Installation Guide

Polypropylene (PP) Common Venting Installation Instructions 22
Copyright © 2018 Rinnai America Corporation. All Rights Reserved.
Combuson Air Requirements
Combuson air provided to the system should not
be taken from any area of the structure that may
produce a negave pressure (i.e. exhaust fans, pow-
ered venlaon fans).
NOTICE
Using Indoor Air For Combuson
When using air from other room(s) in the building, the
total volume of the room(s) must be of adequate
volume (Greater than 50 cubic feet per 1000 Btu/hr).
Each Combuson air opening must have at least one
square inch of free area for each 1000 Btuh, but not
less than 100 square inches each.
When communicang directly with the outdoors
through horizontal ducts, each opening shall have a
minimum free area of 1 in
2
/2000 Btu/hr (1100 mm
2
/
kW) of total input rang of all appliances in the
conned space.
Note: If ducts are used, the cross seconal area of the
duct must be greater than or equal to the required
free area of the openings to which they are
connected.
When communicang indirectly with the outdoors
through vercal ducts, each opening shall have a
minimum free area of 1 in
2
/4000 Btu/hr (550 mm
2
/
kW) of total input rang of all appliances in the
conned space. Combuson air to the appliance can
be provided from a well venlated ac or crawl
space.
WARNING
TO PREVENT POSSIBLE PERSONAL INJURY OR DEATH
DUE TO ASPHYXIATION,
COMMON VENTING WITH OTHER MANUFACTURER’S
INDUCED DRAFT APPLIANCES IS NOT ALLOWED.
Verify proper clearances around the vents.
Ensure that the Combuson Air Requirements
are followed that will provide sucient
combuson air for the appliance.
Ensure approved venng components have been
used.
All horizontal vent runs must be sloped up away
from the water heater a minimum of 1/4”(6 mm)
per foot.
Verify that there is adequate combuson air.
Installaon complies with
Naonal Fuel Gas
Code, ANSI Z223.1/NFPA 54
as well as local and
state regulaons therein.
Checklist for Combuson Air and
Venng Requirements
(Be sure to also maintain 12” above grade or
ancipated snow level)
Vent terminaon per ANSI Z223.1/NFPA 54. For
clearances not specied in ANSI Z223.1/NFPA 54,
clearances are in accordance with local
installaon codes and the requirements of the gas
supplier.
Exhaust