Installation Guide

Polypropylene (PP) Common Venting Installation Instructions 28
Copyright © 2018 Rinnai America Corporation. All Rights Reserved.
Installaon Instrucons
Recommended Spacing of Water Heaters
Spacing of the water heaters is crical for the common
vent system to mounng easily and securely. The
common vent headers are made for 20.5” spacing (center
line to center line) between water heaters. If a dierent
spacing is needed, please contact Rinnai concerning your
applicaon. Rinnai recommends using the Tankless Rack
System (TRS) which is designed for 20.5” spacing. The
engineered system is designed to make installaon simple
and greatly reduces installaon me.
Custom Water Heater Spacing
If common venng with LESS than 20.5” between water heaters:
The installer assumes all responsibility of following local codes. Inspectors can reject the installaon if the
rang plate cannot be seen for all water heaters.
The Exhaust Header and 3” Diameter Extension Pieces must be cut appropriately to maintain the required
3° slope.
If common venng with GREATER than 20.5” between water heaters:
The vent extension and 3” Diameter Extension Pieces must be cut to the appropriate length between to
maintain a 3° slope.
The length of each addional vent extension must be considered in the maximum allowable vent length.
Exhaust Vent Installaon Procedures:
To maintain a 3° slope, use the following
formula to calculate 3” Diameter Extension
Piece length (L):
(L) = (water heater spacing) X 0.05
Example: if the adjacent water heater is
20.5” away
Length (L) = 20.5” x 0.05 = 1.02”
Example: if the adjacent water heater is 26”
away
Length (L) = 26.0” x 0.05 = 1.30”
20.5”
Vent extension
cut to size
Air Intake
extension
3” Diameter
Extension Piece