Installation Guide
Polypropylene (PP) Common Venting Installation Instructions 19
Copyright © 2018 Rinnai America Corporation. All Rights Reserved.
Horizontal Terminaon Clearances
This appliance along with the Common Vent System is cered with the 3”, 4”, 6” Wall Terminaon mounted
in the orientaon shown below.
The exhaust and combuson air terminaons must follow these clearances:
• 12 inch minimum vercally from boom of combuson air terminaon to ground or ancipated snow
line.
• 12 inch minimum from edge of exhaust terminaon to edge of combuson air terminaon.
There should be a minimum of 36 inch between exhaust terminaons in mulple common vent installaons.
Refer to the Rinnai installaon and operaon manual for maximum vent lengths based on the vent diameter
installed.
NOTE: During colder weather when the exhaust
temperature is much hoer than the outside air, the
exhaust fumes will condense, producing water vapor.
As a result a plume of water vapor may be seen leaving
the exhaust.
EXHAUST
VENT
COMBUSTION
AIR VENT
Vent Size Separaon Distance
3”, 4”, 6” 12” Minimum
• MINIMUM 12”
From Exhaust Vent to Combustion Air Vent:
• Minimum 12”
COMBUSTION AIR IS NOT ALLOWED
IN THE SHADED AREA
Combustion
Air Vent
Combustion
Air Vent
Combustion
Air Vent
Combustion
Air Vent
Combustion
Air Vent
Min 12” above grade or
anticipated snow level
Exhaust
Vent