Installation Sheet

Installation & Servicing Instructions Rinnai E-Series
50
Freeze protection
Freeze protection for new or existing systems must use glycol that is specially
formulated for this purpose. This includes inhibitors, which prevent the glycol from
attack the metallic components. This should be for multi-metallic components.
Makecertaintocheckthatthesystemuidiscorrectfortheglycolconcentrationand
inhibitor level. The system should be tested at least once a year and as recommended
by the producer of the glycol solution. The allowed maximum concentration is 50%.
Use only Rinnai approved inhibitors. See below for an approved list of inhibitors.
Use only inhibited propylene glycol solutions, which are specially formulated
for central heating systems. Ethylene glycol is toxic and can attack gaskets
and seals used in the boiler and system. Approved glycols are listed below.
Additives in the installation water are not permitted.
Approved antifreeze: • Rhomar RhoGard Mutli-Metal (AL safe) • Sentinel X500
(max. concentration 50%) • Noble Noburst AL • Fernox Alphi 11
Approved system cleaner: • Noble Noburst Hydronic System Cleaner • Fernox F3 Cleaner
Rhomar Hydro-Solv 9100 Sentinel X400
The system cleaners from NoBurst, Rhomar, and Fernox are not to be used in
the boiler. The boiler must be closed o󰀨 (valved o󰀨) from the rest of the system
or not connected while the cleaners are in the system. The system should then
be drained and then thoroughly ushed with clean water to remove all the
system cleaner.
Approved inhibitors: • Rhomar Pro-tek 922 • Sentinel X100
• Noble Noburst AL inhibitor
10.2 Filling the heating system
Forllingortoppingo󰀨theinstallationyouusethellingloopaccordingtothefollowing
procedure:
1 Switch on the power supply;
2 The display will show FILL;
3 Allfunctionso󰀨(heating , DHW and pump );
4 Pushbrieythe'STEP'-button:PXX(XX=waterpressureinPSI);
5 Openthellingloop(Indicationondisplayincreases);
6 Fill up slowly to 16 to 18 PSI;
7 STOP appears on the display;
8 Closethellingloop;
9 De-aerate the complete installation, start at the lowest point;
10 Check the water pressure and if necessary top it up;
11 Closethellingloop;
12 Activate the functions in use (heating , DHW and/or pump );