Installation Sheet

Installation & Servicing Instructions Rinnai E-Series
49
10 Starting up: Filling and de-aerating the boiler and installation
CAUTION
Observe the following rules of safety:
- All work on the unit must take place in a dry environment.
- Rinnai units may never be in operation without their housing, except in connection
with maintenance or adjustments (see Chapter 132 and 14).
- Never allow electrical or electronic components to come into contact with water.
NOTICE
Carry out the following tasks in connection with maintenance, etc. to an already-
installed unit:
- Shut down all programs
- Closethegasshuto󰀨valve
- Shuto󰀨thepoweratthemainpowerswitch
- Close the service valves (system supply and return)
NOTICE
Take note of the following when maintenance or adjustments are needed:
- The unit must be able to function during these activities; for this reason, the unit’s
supply voltage, gas pressure and water pressure must be maintained. Ensure that
this is not a source of potential danger during these activities.
Following maintenance or other activities; always check the installation of all
parts through which gas ows (with bubble test using leak-search spray).
10.1 Requirements of the water system
Beforellingtheheatingsystem,thecompletesystem,includingallzones,mustbe
thoroughlycleanedand ushedtoremove sediment.Flushuntil clean waterruns
freeofsediment.Rinnaisuggestsusinganapprovedsystemcleanertoushthe
system, but not the boiler. Always use Rinnai approved antifreezes. See the list at
the end of this chapter. Never use reverse osmosis, deionized, or distilled water for
llingtheheatingsystem.
Do not use petroleum-based cleaning or sealing compounds in the boiler
system. Damage of seals and gaskets in boiler and system could occur,
resulting in property damage.
Thecentralheatinginstallationneedstobelledwithpotablewater.
Use only potable water or approved glycol for lling the heating system.
When the water hardness of the lling water exceeds > 10.5 gpg (200 mg/L) the
water has to be treated until below the maximum value of 10.5 gpg (200 mg/L).
The pH value of the installation water must be between 6.5 and 8.5.
Check the pH value using proper equipment or by having the water analyzed by a
water treatment company.
IfpHdi󰀨ersfromabove,contactRinnaiengineeringforfurtherassistance.
Component or product damage as a result of failing to adhere to the water
quality requirements will not be covered by the limited warranty.
!
CAUTION
NOTICE
i
NOTICE
i
NOTICE
i
!
WARNING
!
WARNING
!
WARNING