Owner's Manual
8 C199 Manual
An unconned space is dened in Naonal Fuel Gas
Code, ANSI Z223.1/NFPA 54 as “a space whose vol-
ume is not less than 50 cubic feet per 1000 Btu/hr
(4.8 m3 per kW per hour) of the aggregate input
rang of all appliances installed in that space. Rooms
communicang directly with the space in which the
appliances are installed, through openings not fur-
nished with doors, are considered a part of the un-
conned space.” If the “unconned space” containing
the appliance(s) is in a building with ght construc-
on, addional outside air may be required for proper
operaon. Outside air openings should be sized the
same as for a conned space.
Small Room, Closet, Alcove, Ulity Room, Etc.)
A conned space is dened in the Naonal Fuel Gas
Code, ANSI Z223.1/NFPA 54 as "a space whose vol-
ume is less than 50 cubic feet per 1000 Btu/hr (4.8 m3
per kW per hour) of the aggregate input rang of all
appliances installed in that space." A conned space
must have two combuson air openings. Size the
combuson air openings based on the BTU input for
all gas ulizaon equipment in the space and the
method by which combuson air is supplied:
When sizing the permanent opening consideraon
must be taken for the design of the louvers or grills to
maintain the required free area required for all gas
ulizing equipment in the space. If the free area of
the louver or grill design is not available, assume
wood louvers will have 25% free area and metal
louvers or grills will have 75% free area. Under no
circumstance should the louver, grill or screen have
openings smaller than 1/4”.
Example:
Wood: 10 in x 12 in x 0.25 = 30 in
2
Metal: 10 in x 12 in x 0.75 = 90 in
2
Common Vent & Commercial Hybrid System Applicaons Only
To maintain proper circulaon of combuson air two
permanent openings (one upper, one lower) must be
posioned in conned spaces. The upper shall be
within 12 inches of the top of the conned space and
the lower opening shall be within 12 inches of the
boom of the conned space. Openings must be
posioned as to never be obstructed.
Outdoor air can be provided to a conned space
through two permanent openings, one commencing
within 12 in. (300mm) of the top and one commenc-
ing within 12” (300mm) of the boom, of the con-
ned space. The openings shall communicate to the
outside by one of two ways:
Exhaust
Vent terminaon per ANSI Z223.1/NFPA 54.
For clearances not specied in ANSI Z223.1/
NFPA 54, clearances are in accordance with
local installaon codes and the require-
ments of the gas supplier.
(Be sure to also maintain 12” above grade or
ancipated snow level)