Owner's Manual

C199 Manual 21
Comply with the exhaust clearances found in the Rinnai Installaon and Operaon Manual.
Only one appliance can be aached to the vent system.
Install the system in according to the Centrotherm installaon instrucons.
The vent terminaon and air intake must be in the same pressure zone.
Do not exceed maximum straight vent length with number of elbows as shown in the tables in the following
secon.
Maintain the clearances shown in the gures below.

The following vent materials are for use with this appliance:
Cellular core PVC/CPVC
Radel, ABS, and/or Galvanized ducts.
Failure to use approved vent materials can result in property damage, personal injury, or death.

Flue Installaon with Centrotherm Venng (indoor models only)
Install the venng terminaon according to the diagrams and instrucons below.

11”
5”
Intake
Oponal
Intake
Vent
Slope horizontal exhaust run towards the water heater 1/4” per foot. slope combuson air pipe towards unit. Be
sure to dispose of condensate per local codes.
Combuson Air Pipe
12” Minimum
Exhaust Pipe
12” Minimum above
ancipated snow level
12” Minimum above
ancipated snow level
Combuson Air Pipe
12” Minimum
Exhaust Pipe
Exhaust
Exhaust
Combuson Air Intake