Owner's Manual

16 C199 Manual
Venng Guidelines

Do not use cellular core PVC/CPVC.
Do not use Radel, ABS, or galvanized material to
vent this appliance.
Do not cover non-metallic vent pipe and ngs
with thermal insulaon.
Do not combine vent components from dierent
manufacturers.
Vent diameter must not be reduced.
Do not connect the venng system with an
exisng vent or chimney.
Do not common vent with the vent pipe of any
other manufacturer’s water heater or appliance.
Rinnai water heaters can only be common vented
using a Rinnai cered common vent system.

This water heater is a direct vent water heater and
therefore is cered and listed with the vent
system. You must use vent components that are
cered and listed with the water heater model.
The vent system must vent directly to the outside
of the building and use outside air for combuson.
Excepons:
- Approved Rinnai Common Vent Applicaons
- Commercial Hybrid System Applicaons
Avoid dips or sags in horizontal vent runs by
installing supports per the vent manufacturer’s
instrucons.
Support horizontal vent runs every four feet and
all vercal vent runs every six feet or in
accordance with local codes.
Venng should be as direct as possible with a
minimum number of pipe ngs.
Vent connecons must be rmly pressed together
so that the gaskets form an air ght seal.
The vent piece connected to the water heater
must be secured with one self-tapping screw.

Refer to the instrucons of the vent system
manufacturer for component assembly
instrucons.
If the vent system is to be enclosed, it is suggested
that the design of the enclosure shall permit
inspecon of the vent system. The design of such
enclosure shall be deemed acceptable by the
installer or the local inspector.

If it becomes necessary to access an enclosed vent
system for service or repairs, Rinnai is not responsible
for any costs or dicules in accessing the vent
system. The warranty does not cover obtaining
access to a vent system in an enclosed environment.