Specifications

RIGOL Chapter 2 Command System
2-20 M300 Programming Guide
CONFigure?
Syntax
CONFigure? [(@<ch_list>)]
Description Query the current configuration of the specified channels.
Parameters
Name
Type
Range
Default
<ch_list>
Channel
List
One or more channels (for the multiplexer
channels, DIO channels or TOT channel),
the rules are as follows:
(@101): channel 01 on the module in Slot1;
(@101:103): channel 01 through 03 on the
module in Slot1;
(@101:103,301): channel 01 through 03 on
the module in Slot1 and channel 01 on the
module in Slot3.
If the parameter
is omitted, this
command will be
applied to the
whole scan list.
Explanation The specified channels can only be multiplexer channels, DIO channels and TOT
channels.
If the scan list is empty, the instrument will generate an error when you send the
CONF? command.
If the DMM module is not installed or is disabled, then no DMM-related configurations
are allowed on the multiplexer channels. However, scan is allowed on the digital input
and totalizer channels even when the DMM module is not installed or enabled.
The CONFigure command does not place the instrument into the wait-for-trigger
state. You can send the
INITiate or READ? command with the CONFigure command to
place the instrument into the wait-for-trigger” state.
The
*RST command will clear the scan list and set all the measurement parameters to
their factory settings (refer to
Appendix A: Factory settings). The Instrument Preset
(the
SYSTem:PRESet command) will not clear the scan list but will clear the reading
memory.
Return
Format
The query returns the configurations (for the details, refer to the table below) of the
specified channels in string enclosed in double quotation marks. Multiple return values are
separated by commas.
multiplexer
channels
Function:
CURR
CURR:AC
VOLT
VOLT:AC
RES
FRES
FREQ
PER
TEMP <Temperature sensor
type>,<Temperature Sensor Model>
SENSOR <Anysensor type>
Range
Return the
specified
value in
scientific
notation
Resolution
Return the
specified value
in
scientific
notation
DIO
channels
Function:
DIG
Status:
INP
OUTP
Width:
BYTE
WORD
DWORD
TOT
channels
Function:
TOT
Mode:
READ
RRES
--