User manual
Chapter 2 Command System RIGOL
DP700 Programming Guide 2-35
Related Commands
:SYSTem:RWLock[:STATe]
:SYSTem:LOCal
:SYSTem:LANGuage:TYPE
Syntax
:SYSTem:LANGuage:TYPE <type>
:SYSTem:LANGuage:TYPE?
Description
Selects the system language.
Queries the currently selected language.
Parameter
Name Type Range Default
<type> Discrete {EN|CH} --
Remarks
DP700 series power supply provides the help information, prompt message, and interface display in both
Chinese and English version.
Example
:SYSTem:LANGuage:TYPE EN /*Selects English as the system language*/
:SYSTem:LANGuage:TYPE? /*Queries the currently selected language*/
Return Format
English or Chinese
:SYSTem:LOCal
Syntax
:SYSTem:LOCal
Description
Enables the power supply to shift from the remote mode to the local mode.
Remarks
When the power supply is in the remote mode, sending this command will enable the power supply to
shift from the remote mode to the local mode.
When the power supply is locked in the remote mode, you can send the command to enable the power
supply to return to the local mode. At this time, the remote locking will be disabled.
After the power supply returns to the local mode, all the keys and the knob on the front panel are
available to use. The icons
and will not be displayed on the status bar of the user interface.
Related Commands
:SYSTem:KLOCk:STATe
:SYSTem:RWLock[:STATe]
:SYSTem:REMote