Datasheet
Control devices for safety light barriers
Printing 11.03.2016
DEVICE SAFE L.2
Emer
g
enc
y
sto
p
rela
y
APPLICATIONS
for safety light curtains / barriers
APPROVALS
CE, TÜV, UL, C-UL
CONTACTS
3 normally open safety
LED indicators for status and supply diagnostic
SPECIAL CHARACTERISTICS
Without opposite polarity between channels
start control choosable by a extern bridge
LED
Power, channel 1, channel 2 and restart interlock
24 V DC (electronic fuse)
OPERATING VOLTAGE
POWER CONSUMPTION
ca. 2,5 W
START UP DELAY / FALLBACK TIME
<50 ms / <30 ms
CONTACT CAPACITY max.
6 A, 250 V AC, 24 V DC
CONTACT CAPACITY min. at 24 V DC (*)
10 mA
SIMULTANEITY
Simultaneous: ca. 40 ms
ENVIRONMENTAL TEMPERATURE
- 25 °C to + 55 °C
SWITCHING CAPACITY
1500 VA (resistive load)
CONTACT SECURITY
6 A quick acting or 4 A time lag
OPERATING MODE
(*) We offer all devices who have a CONTACT CAPACITY of
min. 100 mA at 24 V DC with hard gold-plated contacts.
In this way the CONTACT CAPACITY of min. 100 mA is only 4 mA.
Please ask our sales team!
CONNECTION DIAGRAM
A supply voltage must be applied to terminals A1 and A2. The "Power"
and "restart interlock" LED´s illuminate. If this is done, a voltage of 24 V
DC is available on the terminal S11. Terminals S12 and S22 must be
wired as shown in the application examples. To start the module, the
terminals Y1 and Y2 must be bridged over normally open contact. In the
following the contacts 13-14, 23-24 and 33-34 are closed.
The LED´s of channel 1, channel 2 are illuminate and "restart interlock"
must be switched off. In series to the start-button, wired on terminals Y1
and Y2, an external contactor can be controlled. Monitoring of the reset
circuit can be configured by external bridge between terminals BR1 an
BR2.
For version with detachable clamps (screw - or cage clamps) ...
please ask our sales team!
Y1
S12 S22
Y2
Start
BWS-Empfänger
ESPE - receiver
PNP PNP
A1 + 24 V DC
A2 0 V DC
FUNCTION CIRCUIT DIAGRAM
Überwachungslogik /
control logic
K2
K1
elektr.
Sicherung /
electr. fuse
A1
S12
(+)
BR1S11 BR2
S22
Y1
Y2
2313 33
K2
K1
(-)
A2
~
~
=
+
-
~
~
24
14
34
Certifications according to
Safety relevant substance data
Depending on wiring (only max. achievable values are given)
EN ISO 13849-1: PLe, Cat. 4
MTTFd: 36,16 years / high, DC: 99% / high,
CCF: achieved