Datasheet
www.riello-ups.com
MODELS SDL 6500 TM SDL 8000 TM SDL 10000 TM
POWER 6500VA/5200W 8000VA/6400W 10000VA/8000W
INPUT
Nominal voltage 400 Vac Three-phase + N
Minimum voltage (F + N) 164 Vac @ load 100% / 84 Vac @ load 50%
Nominal frequency 50 or 60 Hz ±5Hz
Power factor > 0.95
BY PASS
Voltage tolerance 180 - 264 Vac (selectable in Economy Mode or Smart Active Mode)
Frequency tolerance Selected frequency ±5% (selectable by user)
OUTPUT
Nominal voltage 220-230-240 Vac selectable
Voltage distortion < 3% with linear load / < 6% with non-linear load
Frequency 50 or 60 Hz selectable
Static variation 1.5%
Dynamic variation ≤ 5% in 20 ms
Waveform Sinusoidal
Crest factor 3 : 1
BATTERIES
Charging time 4-6 hours
OVERLOAD TIMES
100% < Load < 110% 1 minute
110% < Load < 150% 4 seconds
Load > 150% 0.5 seconds
OTHER FEATURES
Net weight (kg) 91 94 95
Gross weight (kg) 99 102 103
Dimensions (
hwd
) (mm)
2 x 660x175x455 / 2 x 4Ux19”x660
Packaging dimensions
(
hwd
) (mm)
780 x 555 x (270+15)
Smart Active Output
up to 98%
Protection devices Overcurrent - short-circuit - overvoltage - undervoltage - thermal - excessive low battery protection devices
Communication USB / RS232 + slot for communications interface
Input sockets Terminal board
Output socket Terminal board + 2 IEC 320 C13
Regulations EN 62040-1 EMC EN 62040-2 Directive 73/23 - 93/68 - 2004/108 EC EN 62040-3
Ambient temperature 0°C / +40°C
Relative humidity < 95% non-condensing
Colour Dark grey RAL 7016
Noise level < 45 dBA a 1 m
Standard equipment
provided standard
Two cable guides; terminal board connections; One IEC-16A plug;
software; serial cable; keys to release mimic panel; handle kit