Datasheet
72
Contacts/EPOboard
MultiCOM382providesasetofrelaycontactstoprovideUPSalarmandstatusindication.
Thecontactsareconnectedthroughterminalconnections.SignalcontactsincludeEmergencyPowerOff(EPO),RemoteShutDown(RSD),OnBattery,On
Bypass,AlarmandLowbattery.Thecontactsarechangeoverornormallyopen.
•Max.3Acurrentat250Vac
•Signalcontactcustomisation
Protocolconverter
MultiI/OhasconfigurableinputandoutputsignalcontactstoallowUPSintegrationwithcontrolsystems.Itcanbeusedtoconnecttwodevicestoasingle
UPSserialcommunicationport.ItcanalsocommunicateusingtheMODBUS/JBUSprotocolonRS485lines.
•8analog/digitalinputs
•8relayoutputstomonitorUPSandmainsstatus
•ItcancontroltwoindependentRS232/RS485seriallinestomonitor
theUPSanditsoperatingstatesusingtheMODBUS/JBUSprotocol
•Firmwareupgradeablethroughtheserialport
TheI/Oexpansioncard,fortheMasterPlusrange,isequippedwith:
•6outputswithvoltage-freeNC/NOcontacts(250V/5A),electricallyisolatedfromeachotherandfromothercircuits
•2self-poweredinputs
Eachoutputorinputcanbeconfiguredwithdifferentmeanings,viatherelativemenu.
Expansioncard