UPS MODEL Back-up Dimensions Weights (Kg) Type Code Battery Module
(HWD) mm modulo to be combined with that of the UPS
batteries with standard back-up)
DLPR100 30 89x483x375 15 BBR 36-14 ACCRC110RU-01
DLPR150 22 133x483x550 18 BBR 60-7 ACCH1R15RU-07
DLPR150 35 178x483x430 30 BCR 60-12* ACCH1R15RU-01
DLPR150 55 178x483x430 57 BCR 60-24* ACCH1R15RU-02
DLPR200 25 178x483x430 35 BCR 72-12* ACCK1R20RU-01
DLPR300 26 178x483x430 40 BBR 120-7 ACCH2R30RU-05
DLPR300 35 178x483x430 52 BCR 120-12* ACCH2R30RU-01
49
data
Technical
DLPR70 DLPR100 DLPR150 DLPR200 DLPR300
POWER 700VA/450W 1000VA/700W 1500VA/1050W 2000VA/1400W 3000VA/2100W
INPUT
Rated voltage 220-230-240 VAC
Voltage range
for non intervention of the battery
170-276
Rated frequency 50 - 60 Hz ±5 Hz
Frequency 50 Hz
Maximum current 3.5 A 5 A 7.4 A 10 A 14.4 A
Rated current 2.5 A 3.5 A 5.2 A 6.8 A 10.2 A
Power factor
0.93
0.93
0.99
0.99
0.99
BY PASS
Voltage range
for switching
180-264 Vac
Frequency range
for switching
selected frequency ± 5 Hz
BATTERY
Transfer time (mains power failure) nil
Recharge time 5 - 7 h 5 - 7 h 5 - 7 h 4 - 6 h 5 - 7 h
OUTPUT
Rated voltage 230 Vac ± 1.5% 230 Vac ± 1.5% 220 or 230 or 240 Vac selectable ± 1.5%
Waveform sinewave
Voltage distortion < 2%
50 or 60 Hz with 50 or 60 Hz with 50 or 60 Hz 50 or 60 Hz 50 or 60 Hz
Frequency
autom. autom. selection selectable selectable selectable
Crest factor of the current 3 : 1
Rated power in VA 700 1000 1500 2000 3000
Rated power in W 450 700 1050 1400 2100
OTHER DATA
AC/AC efficiency 89 % 89 % 89 % 90 % 90 %
Operating temperature 0 - 40 °C
Humidity < 90 % non condensing
Low battery – overcurrent - short-circuit
Protection
overvoltage – undervoltage - temperature
Safety compliance EN 50091 - 1 - 1 and Directive 73 / 23 / EEC
EMC conformance EN 50091 - 2 cl. B and Directive 89 / 336 EEC
Surge capability IEC 801-5 6KV 1.2/50usec; 3KA 8/20usec
Color dark gray RAL 5004
Noise < 40 dBA at 1 m
MODELS
Description Power Back-up Dimensions Weights Code
(min) (HWD) mm (Kg)
Dialog Plus Rack DLPR70 700VA/450W 8 89x483x390 7 URC10705XXRU
Dialog Plus Rack DLPR100 1000VA/700W 10 89x483x390 10 URC1R1006XXRU
Dialog Plus Rack DLPR150 1500VA/1050W 11 178x483x490 24 UX1R1506XXRU
Dialog Plus Rack DLPR200 2000VA/1400W 11 222x483x490 27 UX1R2006XXRU
Dialog Plus Rack DLPR300 3000VA/2100W 13 178x483x550 43 UX2R3008XXRU
* Includes auxiliary battery charger for faster recharging
Table Codes
weights,
dimensions
Back-up
extension
modules
Options
Description Dimensions (HWD) mm Weight (Kg) Code
External manual by-pass 89x483x380 2 ACCBYPXXNP-01
Communications software (full version) see software pag. 64 (PowerShield
2
standard version included)