Specifications

/
45
DAR 50 DAR 75 DAR 100 DAR 150 DAR 200
POWER 500VA/335W750VA/500W1000VA/670W1500VA/1000W2000VA/1340W
INPUT
Rated voltage 230 VAC
Range with mains supply present 230V (-25 / + 21)%
Frequency 50 – 60 Hz with autorange
Frequency range ± 5 Hz CITA
OUTPUT
Rated voltage 230 VAC
Voltage in mains operation 230 V (-15 / +11%)
Frequency 50 – 60 Hz with autorange
Voltage in battery operation 230V + 5%
Waveform Sinewave
Distortion <2%
BATTERY
Type Maintenance-free sealed lead-acid
Recharge time 8 h
OTHER DATA
Operating temperature 0 ÷ 40 °C
Humidity <90%
Overload – short-circuit – overvoltage – undervoltage – temperature
Protection
low battery
Safety compliance EN 50091-1-1 and Directives 73 / 23 EEC and 93 / 68 EEC
EMC conformance EN 50091 – 2 cl. B and Council Directive 89 / 336 EEC
Surge capability IEC 801-5 6 KV 1.2 / 50 µsec ; 3 KA 8 / 20 µsec differential
Color dark gray RAL 5004
Noise < 40 dBA at 1 m.
MODELS
(min)(HWD) mm(Kg)
Dialog Active Rack DAR50 500VA/335W 13 89x483x450 19 ULR1050835RU
Dialog Active Rack DAR75 750VA/500W 8 89x483x450 20 ULR1070535RU
Dialog Active Rack DAR100 1000VA/670W 8 89x483x450 21 ULR1100535RU
Dialog Active Rack DAR150 1500VA/1000W 10 133x483x450 26 ULR1150635RU
Dialog Active Rack DAR200 2000VA/1340W 10 133x483x450 34 ULR2200635RU
By-pass manuale 89x483x380 2 ACCBYPXXNP-01
Communication software See software section page 64
Back-up extension modules
UPS MODEL* Back-up* Dimensions Weights Type  Code (to be combined a
(HWD) mm Kg UPS with standard back-up)
DAR200 22’ 133x483x550 18 BBR60-7 ACCH1R15RU-07
30’ 178x483x430 30 BCR60-12* ACCH1R15RU-01
60’ 178x483x430 57 BCR60-24* ACCH1R15RU-02
* includes auxiliary battery charger for faster recharge
Table Codes
weights, dimensions
Description Power Back-up Dimensions Weights Code
data
Technical