Specifications

41
Back-up extension modules**
Table Codes
weights, dimensions
Description Power Dimensions Weights Code
(HWD) mm (Kg)
Master Dialog RT10000 100kVA/80kW 1400x1070x740 650 UMRT1K0045RU
Master Dialog RT12000 120kVA/96kW 1400x1070x740 730 UMRT1K2045RU
Master Dialog RT16000 160kVA/128kW 1400x1070x740 900 UMRT1K6045RU
For parallel UPS (with parallel kit included) add -02 to the UPS code
(ex. RT10000 parallelable = UMRT1K0045RU-02)
Options
Cabinets/batteries
Description Dimensions Weight Code
(HWD) mm (Kg)
Empty cabinet for 36/40 batt.
max 100Ah, including 1800x860x740 190 ACCMRM20NP-18
connection cable kit
Battery type 1265 190x350x166 23,5 0604030006
Battery type 1280 183x355x167 24 0604030013
Battery type 12100 227x330x171 32 0604030046
1400x270x740 180 ACCMRM100NP-01
1400x270x740 180 ACCMRM120NP-01
Description Dimensions Weights Code
(HWD) mm (Kg)
Isolation transformer
module for RT10000
1400x640x720 480 ACCMRT100NP-01
Isolation transformer
module for RT12000
1400x640x720 500 ACCMRT120NP-01
Isolation transformer1400x640x720500see price list
module for RT16000
RT10000 CLEAN (THDi<5%)
RT12000 CLEAN (THDi<5%)
RT16000 CLEAN (THDi<5%) 1400X270X740 200 ACCMRM160NP-01
Kit for connection in parallel / / ACCMRM20NP-11
Remote control panel with LCD / / ACCMRM20NP-05
LED-based remote control panel (see picture page 20) / ACCMRT20NP
Communication software (full version) see software section page 64 (PowerShield
2
standard version included)
UPS MODEL* Back-up Back-up Dimensions (HWD) Weights (Kg) Type
Power factor 0.8 Power factor 0.7 Battery Module Batt. Mod.
Master Dialog 7’ 8’ 1800x860x740 1030 36 batt. 1265
RT 10000 10’ 12’ 1800x860x740 1054 36 batt. 1280
15’ 17’ 1800x860x740 1342 36 batt. 12100
20’ 23’ 2x(1800x860x740) 2072 72 batt. 1265
26’ 30’ 2x(1800x860x740) 2108 72 batt. 1280
35’ 40’ 2x(1800x860x740) 2684 72 batt. 12100
60’ 70’ 3x(1800x860x740) 4026 108 batt. 12100
Master Dialog 7’ 8’ 1800x860x740 1130 40 batt. 1265
RT 12000 10’ 12’ 1800x860x740 1150 40 batt. 1280
12’ 14’ 1800x860x740 1470 40 batt. 12100
18’ 19’ 2x(1800x860x740) 2260 80 batt. 1265
23’ 25’ 2x(1800x860x740) 2300 80 batt. 1280
32’ 35’ 2x(1800x860x740) 2940 80 batt. 12100
52’ 60’ 3x(1800x860x740) 4410 120 batt. 12100
60’ 70’ 4x(1800x860x740) 4600 160 batt. 1280
Master Dialog 9’ 11’ 1800x860x740 1470 40 batt. 12100
RT 16000 14’ 16’ 2x(1800x860x740) 2260 80 batt. 1265
24’ 27’ 2x(1800x860x740) 2940 80 batt. 12100
30’ 35’ 3x(1800x860x740) 3390 120 batt. 1280
50’ 57’ 4x(1800x860x740) 5880 160 batt. 12100
* Different back-up values are available on request. Other types of batteries are also available (long life; open pot;
Nickel Cadmium)
**In view of the dimensions and weight of the battery modules, these will be assembled at the installation site.
The No. and type of batteries + No. of cabinets must be specified in this order:
for example 36 batteries 1265 on 1 cabinet: code = 36 x (0604030006) + 1 x (ACCMRM20NP-18)