Specifications
33
CHARACTERISTICS
• reliable, stabilized, filtered voltage
(double on-line conversion technology
(VFI according to EN50091-3 specifications) with filters
for suppression of atmospheric disturbances
• high level reliability of the UPS assured by:
- extremely high short-circuit current (2.8In);
this makes the UPS compatible with
even the most difficult applications: transformers,
lighting, drives, industrial processes)
- full microprocessor redundant control
(2 microprocessors)
- isolation transformer on inverter output
- IGBT technology
.
• its 0.8 power factor makes it suitable for
powering of IT and industrial loads
• high level diagnostics: event log, states,
measurements, alarms available on standard
multi-language LCD display
• maximum care of the batteries
temperature-dependent recharge
• protection against deep battery discharge
• simple to install:
- possibility of inserting the UPS on any
distribution system (neutral not
required on rectifier input).
Possibility of separating the
rectifier/bypass power networks and of
powering
these with 2 even separate sources, without
the need for galvanic isolation
(necessary on certain UPS without output
transformer).
- possibility of regulating the output voltage
(to offset voltage drops on the cables)
• maximum reliability and availability of power
(parallel distributed up to 6 units for redundant
(N+1) or power parallel)
• standard BACK FEED protection, against
power return on the mains in the case of fault
• low consumption: assured by the selectable
ECO-MODE function that makes it possible to
power from the mains, when this is stable,
guaranteeing very high efficiency (›98%,
RT10000/RT16000 models)
ADVANCED COMMUNICATION
• advanced, multi-platform communication, for all
operating systems and network environments:
PowerShield
2
supervision and shut-down
software included, with SNMP agent, for Windows
95, 98, 2000, Me, XP, Mac OSx, 9.x, Linux, NT
4.0, Novell operating systems.
The UPS is equipped with a cable for direct
connection to the PC (Plug and Play)
• RS232 serial port
• clean relay contacts
• ESD (Emergency Switching Device) input for UPS
shut-down using remote emergency button
• input for switching to bypass by remote signal
• digital or LED-based remote control panel
APPLICATIONS
• Local Area Networks (LAN)
• Servers
• Data centers
• Internet centers (ISP/ASP/POP)
• Industrial PLCs
• Electro-medical devices
• Telecommunications devices
• Emergency devices (lights/alarms)
• Industrial processes