Specifications
28
MULTI DIALOG MDM
SINGLE-PHASE MODELS
data
Technical
MDM1000 MDM1500 MDM2000
RECTIFIER INPUT
Rated power [kVA] 10 15 20
Rated voltage 230V single-phase or 400V three-phase + N
Voltage range ± 20 %
Frequency range 45 ÷ 65 Hz
Power factor 0.95
BATTERIES
Type Sealed lead-acid
Recharge time [h] 8
INVERTER OUTPUT
Rated power [kVA] 10 15 20
Active power [kW]* 8 12/10.5* 16/12*
Number of phases 1
Rated voltage [V] 230
Voltage regulation range 200 ÷ 243 V
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Distortion with linear load 2 %
Static stability ± 1 %
Dynamic stability ± 5 % in 10 ms
Frequency 50 / 60 Hz selectable
Overload 125%150%200% of the rated current for 10’/ 1’/7’’
BYPASS
Rated voltage 230V
Number of phases 1
Permitted voltage range ±15 % ( selectable from ± 5 % to ± 25 %)
Rated frequency 50 / 60 Hz
Permitted frequency range ±2 % (selectable from ± 1 % to ± 5 %)
INSTALLATION INFORMATION
Input Single-phase and three-phase
Remote signaling zero-potential contacts
Remote controls ESD and bypass
Communication Double RS232/C
Operating temperature 0 + 40 °C
Relative humidity 95 % (non condensing)
Color Light gray RAL 7035
Audible noise < 56 dBA
Protection rating IP20
Efficiency > 92%
Compliance Safety EN 50091-1 EMC EN 50091-2 Lev. A Directives 73/23-93/68-89/336 EEC
Air flow (m3/h)
320 320 480
(for installations in a closed environment)
Bypass input current 45A 68A 91A
Maximum rectifier
input current
18A 27A 36A
Differential input current 100mA
VALUE OF THE OUTPUT PROTECTIONS FOR SELECTIVITY**
Normal fuses (GI) In (Rated current)/5.5
Normal switches (Curve C) In (Rated current)/5.5
Extra Fast fuses In (Rated current)/2
* With single-phase input.
** Complying with these values, the UPS will be able to provide the power required to interrupt the output protection in
the case of a short-circuit without switching the load to the mains supply.