Specifications
/
24
POWER DIALOG PLUS
MODELS
PWP 600PWP 650PWP800PWP1000
INPUT
Rated voltage 230Vac 230 Vac single-phase or three-phase with neutral
single-phase
Minimum voltage for 170Vac @ 100% load
non intervention of the battery 140Vac @ 50 load%
Rated frequency 50 - 60 Hz ±5 Hz
Power factor
Single-phase Three-phase Single-phase Three-phase Single-phase Three-phase
≥ 0.99≥ 0.99≥0,95≥0,99≥0,95≥0,99≥0,95
Current distortion
Single-phase Three-phase Single-phase Three-phase Single-phase Three-phase
with distorting load ≤ 7%≤ 7%≤ 27%≤ 7%≤ 27%≤ 7%≤ 27%
BY PASS
Voltage range 180 – 264 Vac (selectable in Economy Mode and SMART ACTIVE MODE)
Frequency range Selected frequency ±5 Hz
BATTERY
Typical back-up 12’20’16’12’
Recharge time 6 – 8 h
OUTPUT
Rated voltage 220 / 230 / 240 Vac selectable ± 1%
Static variation 1%
Dynamic variation ≤ 5% in 20ms
Waveform Sinewave
Voltage distortion
with linear load
< 2%
Voltage distortion
with distorting load
< 5%
50 / 60 Hz
Frequency selectable
or with autorange
Crest factor 3 : 1
Rated power in VA/W 6000/42006500 / 46008000 / 560010000 / 7000
OVERLOAD TIMES
100% < Load < 125% 2’
125% < Load < 150% 30 s
Load
150% 0.5 s
INSTALLATION INFORMATION
Input Input Input Input Input Input
Efficiency
Single-phase Three-phase Single-phase Three-phase Single-phase Three-phase
91%91%92%91%92%91%92%
Efficiency
Line-interactive/Smart Active
98%
Operating temperature 0 – 40 °C
Humidity < 90 % non condensing
Protection Low battery – overcurrent – short-circuit - overvoltage - undervoltage – temperature
Compliance EN 50091–1–1, Directives 73 / 23 EEC and 93/68 /EEC EN 50091-2 cl. A, Council Directive 89/336 EEC
Color Light gray RAL 7035
Noise < 40 dBA at 1 mt.
Single-phase Three-phase* Single-phase Three-phase* Single-phase Three-phase*
Maximum input current*
29A31 A11A41 A15 A50 A18 A
Differential input current** 10 mA
VALUE OF THE OUTPUT PROTECTIONS FOR SELECTIVITY***
Normal fuses (GI) In (Rated current)/7
Normal switches In (Rated current)/7
Extra Fast fuses (EF) In (Rated current)/2
* In the case of UPS with three-phase input and single-phase output, the cables and input protections must be calculated
according to the value of the single-phase current in the case in which the UPS switches the load (single-phase)
to input (three-phase). In this case, the single-phase load will be supported entirely on one of the three input phases.
** This value must be added to the differential current of the equipment.
*** Complying with these values, the UPS will be able to provide the power required to interrupt the output
protection in the case of a short-circuit without switching the load to the mains supply.
data
Technical
›
-