Specifications
20
DIALOG PLUS
MODELS
data
Technical
0
10
20
30
40
50
60
CARICO (VA)
AUTONOMIA (MIN)
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
DLP 70
DLP 100
DLP
150
DLP 200
DLP 300
DLP 400
DLP 500
CARICO (VA)
0
250
500
750
1000
1250
1500
1750
2000
2250
2500
2750
3000
3250
3500
3750
4000
4250
4500
4750
5000
0
10
20
30
40
50
60
AUTONOMIA
(MIN)
Back-up graph
DLP70 DLP100 DLP150 DLP200 DLP300 DLP400 DLP500
POWER 700VA/450W 1000VA/700W 1500VA/1050W 2000VA/1400W 3000VA/2100W 4000VA/2400W 5000VA/3500W
INPUT
Rated voltage 220 - 230 - 240 Vac
Voltage range 170–276 Vac 176-276 Vac 170-276 Vac
Rated frequency 50 - 60 Hz ±5 Hz
Power factor > 0.93 > 0.99 > 0.98
Input current Sinewave
BY- PASS
Voltage range 180 - 264 Vac
Frequency range Selected frequency ±5 Hz
BATTERY
Recharge time 5 - 7 h 4 - 6 h 5 - 7 h 6 - 8 h
OUTPUT
Rated voltage 230 Vac ±1.5% 220 or 230 or 240 Vac selectable ±1.5%
Waveform Sinewave
Voltage distortion < 2%
Frequency 50 or 60 Hz autorange 50 or 60 Hz selectable
Crest factor of the current 3 : 1 3.5 : 1 3 : 1
INSTALLATION INFORMATION
AC/AC efficiency 89 % 89 % 89 % 90 % 90 % 90 % 90 %
Operating temperature 0 - 40 °C
Humidity < 90 % non condensing
Protection Low battery - overcurrent - short-circuit - overvoltage - undervoltage - temperature
Compliance EN 50091-1-1 specifications and Council Directive 73 / 23 EEC EN 50091 - 2 cl. B and Council Directive 89 / 336 EEC
Surge capability IEC 801-5 6KV 1.2/50 µsec; 3KA 8/20 µsec
Color Light gray RAL 7035
Noise < 40 dBA at 1 m < 45 dBA at 1 m
Maximum input current 3.5 A 5 A 7.4 A 10 A 14.4 A 16 A 24 A
Diff. input current* 1 mA 1 mA 1 mA 1 mA 1 mA 1 mA 6 mA
* This value must be added to the differential current of the equipment.
Remote mimic panel (leds)