Technical data
Commissioning
2.7 First commissioning, vector control mode in the chassis format
Commissioning Manual
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
97
2.7.1 Task
A drive in the chassis format in the vector control mode with the following components is to
be commissioned for the first time:
Table 2- 12 Component overview
Designation Component Order number
Closed-loop control and infeed
Control Unit Control Unit 320-2DP 6SL3040-1MA00-0AA0
Active Line Module Active Line Module 380 kW / 400 V 6SL3330–7TE36–1AAx
Active Interface Module Active Interface Module 6SL3300–7TE38–4AAx
Drive 1
Motor Module Motor Module 380 A 6SL3320–1TE33–8AAx
Motor Induction motor
Without brake
With encoder
Type: 1LA8
rated voltage = 400 V
rated current = 345 A
rated power = 200 kW
rated power factor = 0.86
rated frequency = 50.00 Hz
rated speed = 989 rpm
cooling type = natural cooling
HTL encoder, 1024 p/r, A/B, R
Drive 2
Motor Module Motor Module 380 A 6SL3320–1TE33–8AAx
Motor Induction motor
Without brake
With encoder
Type: 1LA8
rated voltage = 400 V
rated current = 345 A
rated power = 200 kW
rated power factor = 0.86
rated frequency = 50.00 Hz
rated speed = 989 rpm
cooling type = natural cooling
HTL encoder, 1024 p/r, A/B, R
The enable signals for the infeed and the drive should be realized via terminals.