Technical data
Commissioning
2.5 First commissioning, servo control mode, booksize format
Commissioning Manual
88 Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
What to do? How to do it? Comment
Line contactor Line contactor
p0728.8 = 1 Set DI/DO as output
p0738 =863.1 Line contactor ON
p0860 = 723.9 Line contactor, feedback signal
The line contactor must be
controlled by the infeed_1
drive object.
See function diagram [8934]
In the function --> Line
contactor control screen,
you can check that the
interconnection is correct.
4.
5. Save the parameters
on the device
Connect with target system (go online)
Target system -> Download to target device
Target system -> Copy from RAM to ROM
(save the data on the memory card)
Position cursor on drive unit
(SINAMICS S120) and right-
click.
6. The motor starts to
run.
The drives can be started via the control panel in STARTER.
Once the pulses for the infeed have been enabled the
line/DC link identification will be activated and carried out.
The infeed then switches to operational mode.
For more information about
the control panel, see
Getting Started.
The control panel supplies
the control word 1 (STW1)
and speed setpoint 1
(NSOLL).
For more information about
line/DC link identification,
see the SINAMICS S120
Function Manual.
STARTER diagnosis options
Under "Component" -> Diagnosis -> Control/status words
● Control/status words
● Status parameters
● Missing enable signals