Technical data
Commissioning
2.2 STARTER commissioning tool
Commissioning Manual
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
59
Figure 2-5 Setting online access
Assigning the IP address and the name
Note
ST (Structured Text) conventions must be satisfied for the name assignment of IO devices in
Ethernet (SINAMICS components). The names must be unique within Ethernet.
The characters "-" and "." are not permitted in the name of an IO device.
Note
The IP address and device name for the Control Unit are stored on the memory card (non-
volatile).
Assignment with STARTER, "Accessible nodes" function
Use the STARTER to assign an IP address and a name to the Ethernet interface.
● Connect the programming device (PG/PC) and the Control Unit using a crosslink
Ethernet cable.
● Switch on the Control Unit.
● Open STARTER.
● Either create a new project or open an existing one.
● A search is performed for available nodes in Ethernet via Project -> Accessible nodes or
the "Accessible nodes" button.
● The SINAMICS drive object is detected and displayed as a bus node with IP address
169.254.11.22 and without name.