Technical data
Commissioning
2.2 STARTER commissioning tool
Commissioning Manual
56 Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
Settings in STARTER for direct online connection via PROFIBUS
The following settings are required in STARTER for communication via PROFIBUS:
● Tools -> Set PG/PC Interface...
Add/remove interfaces
● Extras -> Set PG/PC interface... -> Properties
Activate/deactivate "PG/PC is the only master on the bus".
Note
Baud rate
– Connecting STARTER to an operational PROFIBUS:
STARTER automatically detects the baud rate used by SINAMICS for PROFIBUS.
– Connecting STARTER for commissioning:
The Control Unit automatically detects the baud rate set in STARTER.
PROFIBUS addresses
The PROFIBUS addresses for the individual drive units must be specified in the
project and must match the address settings on the devices.
2.2.3 Activating online operation: STARTER via Ethernet
Description
The Control Unit can be commissioned using a programming device (PG/PC) via the
integrated Ethernet Interface. This interface is provided for commissioning purposes only
and cannot be used to control the drive in operation. Routing in conjunction with a CBE20
expansion card is not possible.
Preconditions
● STARTER from version 4.1.5 or higher
STARTER via Ethernet (example)
(WKHUQHW
DGDSWHU
3*3&
(WKHUQHW
LQWHUIDFH
67$57(5
&RQWURO
8QLW
'HYLFH
,3
(WKHUQHW
Figure 2-2 Connecting the programming device to the target device via Ethernet (example)