Technical data
Preparation for commissioning
1.6 Powering-up/powering-down the drive system
Commissioning Manual
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
49
Control and status messages
Table 1- 14 Power-on/power-off control
Signal name Internal control word Binector input PROFdrive/Siemens
telegram 1 ... 352
0 = OFF1 STWA.00
STWAE.00
p0840 ON/OFF1 STW1.0
0 = OFF2 STWA.01
STWAE.01
p0844 1. OFF2
p0845 2. OFF2
STW1.1
0 = OFF3 STWA.02 p0848 1. OFF3
p0849 2. OFF3
STW1.2
Enable operation STWA.03
STWAE.03
p0852 Enable operation STW1.3
Table 1- 15 Switch-in/switch-out status signal
Signal name Internal status word Parameter PROFdrive/Siemens
telegram 1 ... 352
Ready for switching on ZSWA.00
ZSWAE.00
r0899.0 ZSW1.0
Ready for operation ZSWA.01
ZSWAE.01
r0899.1 ZSW1.1
Operation enabled ZSWA.02
ZSWAE.02
r0899.2 ZSW1.2
Pulse inhibit ZSWA.06
ZSWAE.06
r0899.6 ZSW1.6
Pulses enabled ZSWA.11 r0899.11 ZSW2.10
1)
1)
only available in Interface Mode p2038 = 0
Function diagrams (see SINAMICS S120/S150 List Manual)
● 2610 Sequence control - sequencer
● 2634 Missing enable signals, line contactor control
● 8732 Basic Infeed - sequencer
● 8832 Smart Infeed - sequencer
● 8932 Active Infeed - sequencer