Technical data

Preparation for commissioning
1.5 Rules for wiring with DRIVE-CLiQ
Commissioning Manual
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
45
1.5.10.3 Default settings for the sampling times
When commissioning for the first time, the current controller sampling times (p0115[0]) are
automatically pre-set with factory setting values:
Table 1- 13 Factory settings
Construction type Number p0112 p0115[0] p1800
Active Infeed and Smart Infeed
Booksize 1 2 (Low) 250 µs -
Chassis
400 V / ≤ 300 kW
690 V / ≤ 330 kW
1 2 (Low) 250 µs -
Chassis
400 V / > 300 kW
690 V / > 330 kW
1 0 (Expert)
1 (xLow)
375 µs (p0092 = 1)
400 µs (p0092 = 0)
-
-
Basic Infeed
Booksize 1 4 (High) 250 µs -
Chassis 1 3 (Standard) 2000 µs -
Servo
Booksize 1 to 6 3 (Standard) 125 µs 4 kHz
Chassis 1 to 6 1 (xLow) 250 µs 2 kHz
Blocksize 1 to 5 3 (Standard) 125 µs 4 kHz
Vector
Booksize 4 kHz
Chassis
400 V / ≤ 250 kW
1 to 3 only n_ctrl
1 to 6 only U/f
3 (Standard) 250 µs
2 kHz
Booksize 4 kHz
Chassis
400 V / ≤ 250 kW
4 to 6 only n_ctrl
7 to 12 only U/f
0 (Expert) 500 µs
2 kHz
Chassis
> 250 kW
690 V
1 to 4 only n_ctrl
1 to 5 only U/f
1 to 6 only n_ctrl
0 (Expert)
1 (xLow)
0 (Expert)
375 µs (p0092 = 1)
400 µs (p0092 = 0)
500 µs (p0092 = 1)
1.333 kHz
1.25 kHz
2 kHz
Booksize 4 kHz
Chassis
> 6 only U/f 0 (Expert) 500 µs
2 kHz
1 to 3 only n_ctrl
1 to 6 only U/f
3 (Standard) 250 µs 4 kHz Blocksize
> 3 n_ctrl (min. 1)
> 6 only U/f
0 (Expert) 500 µs 4 kHz
Caution
If a Power Module in blocksize format is connected to a Control Unit, the sampling times of all vector drives are set
according to the rules for Power Modules in blocksize format (only 250 µs or 500 µs possible).