Technical data

Diagnostics
3.5 Fault and alarm messages
Commissioning Manual
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
229
Properties of the alarm buffer/alarm history:
The arrangement in the alarm buffer is made after the time that they occurred from 7 to 0.
In the alarm history, this is from 8 to 63.
If 8 alarms have been entered into the alarm buffer, and a new alarm is received, then the
alarms that have been resolved are transferred into the alarm history.
r2121 is incremented each time the alarm buffer changes.
An alarm value (r2124) can be output for an alarm. The alarm value is used to diagnose
the alarm more accurately; please refer to the alarm description for details of the
meaning.
Deleting the alarm buffer, index [0...7]:
The alarm buffer index [0...7] is reset as follows: p2111 = 0