Technical data

Diagnostics
3.2 Diagnostics via STARTER
Commissioning Manual
210 Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
The device cycle clock display flashes 3 times at around 1 Hz when the time slice is changed
from < 4 ms to ≥4 ms (see description under "Properties").
Note
Please refer to the online help for more information about parameterizing and operation.
Properties
Up to 8 recording channels for each trace
When more than 4 channels per single trace are used, the trace's device clock cycle is
switched automatically from 0.125 ms (0.250 ms for vector control) to 4 ms. This action
ensures that the CU320's performance is not influenced too strongly by the trace.
Device clock cycles of SINAMICS S120 trace for single traces:
4 channels: 0.125 ms (Servo)/0.250 ms (Vector)
8 channels: 4 ms (Servo/Vector)
Two independent traces per Control Unit
Endless trace
The parameter data are written to the memory until this is full.
A ring buffer can be selected in order to avoid this. If the ring buffer is active, then
STARTER automatically starts again from the beginning to write to the trace memory
after the last trace parameter was saved.
Device cycle of the SINAMICS S120 trace for an endless trace:
4 channels: 0.125 ms (servo)/0.250 ms (vector)
8 channels: 4 ms (Servo/Vector)
The time slice 4 ms may not be available due to the system condition. In this case the
next higher time slice is used.
Triggering
Without triggering (recording immediately after start)
Triggering on signal with edge or on level
STARTER commissioning tool
Automatic or adjustable scaling of display axes
Signal measurement via cursor
Settable trace cycle: Integer multiples of the basic sampling time
Averaging the trace values
If a float value with a clock cycle slower than the device cycle clock is recorded, then the
values recorded will not be averaged. This is achieved using parameter p4724.
Parameter p4724[0...1] "Trace averaging in time range" is "0" in the default setting.
Index "0" and "1" stand for both the traces each with 8 channels.
If the traced values should be averaged, then parameter p4724 should be set to "1".