Technical data
Diagnostics
3.1 Diagnostics via LEDs
Commissioning Manual
202 Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
3.1.4.4 Terminal Module TM54F
Table 3- 53 Meaning of the LEDs on the Terminal Module TM54F
LED Color Status Description, cause Remedy
- Off Electronics power supply is missing or outside permissible
tolerance range.
–
Green Continuou
s light
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
–
Orange Continuou
s light
DRIVE-CLiQ communication is being established. –
Red Continuou
s light
At least one fault is present in this component.
Note:
The LED is activated irrespective of whether the
corresponding messages have been reconfigured.
Remedy and
acknowledge
fault
Flashing
light 0.5
Hz
Firmware is being downloaded. – Green/red
Flashing
light 2 Hz
Firmware download is complete. Wait for POWER ON Carry out a
POWER ON
READY
Green/orange
or
Red/orange
Flashing
light
Component recognition via LED is activated (p0154).
Note:
Both options depend on the LED status when component
recognition is activated via p0154 = 1.
–
– ON The controllable sensor power supply is functioning fault-
free.
– L1+, L2+,
Red Continuou
s light
There is a fault in the controllable sensor power supply. –
L3+ – ON Sensor power supply is functioning fault-free.
Red Continuou
s light
There is a fault in the sensor power supply.