Technical data

Diagnostics
3.1 Diagnostics via LEDs
Commissioning Manual
196 Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
Table 3- 47 Meaning of the OPT LED on the Control Unit
LED Color Status Description, cause Remedy
OFF Electronics power supply is missing or outside permissible
tolerance range.
Communication Board either defective or not inserted.
Continuous
light
Communication Board is ready and cyclic communication
is taking place.
Green
Flashing light
0.5 Hz
The Communication Board is ready, but cyclic
communications is not running.
Possible causes:
At least one fault is present.
Communication is being established.
Continuous
light
Cyclic communication via PROFINET has not yet been
established. However, non-cyclic communications are
possible. SINAMICS waits for a parameterizing/configuring
telegram
Flashing light
0.5 Hz
The firmware update into the CBE20 has been completed
with an error.
Possible causes:
The CBE20 is defective.
The memory card for the Control Unit is defective.
In this state CBE20 cannot be used.
Red
Flashing light
2 Hz
There is a communications error between the Control Unit
and the CBE20.
Possible causes:
Board was withdrawn after booting.
The board is defective
Correctly insert the
board, if required,
replace.
OPT
Orange Flashing light
0.5 Hz
Firmware is being updated.