Meaning of the LEDs on the CBE20 Communication Board Ethernet
Table 3- 45 Meaning of the LEDs at ports 1 to 4 of the X1400 interface
LED Color Status Description
- Off Electronics power supply is missing or outside permissible tolerance range (link
missing or defective).
Link port
Green Continuous
light
A different device is connected to port x and a physical connection exists.
- Off Electronics power supply is missing or outside permissible tolerance range (no
activity).
Activity port
Yellow Flashing light Data is being received or sent at port x.
Table 3- 46 Meaning of the Sync and Fault LEDs on the CBE20
LED Color Status Description
Off If the link port LED is green:
The CBE20 is operating normally, data is being exchanged with the configured
IO Controller.
Flashing
The response monitoring interval has elapsed.
Communications is interrupted.
The IP address is incorrect.
Incorrect or no configuration.
Incorrect parameter settings.
Incorrect or missing device name.
IO Controller not connected/switched off, although an Ethernet connection
has been established.
Other CBE20 errors
Fault
Red
Continuous
light
CBE20 bus error
No physical connection to a subnet/switch.
Incorrect transmission rate
Full duplex transmission is not activated.
Off If the link port LED is green:
Control Unit task system is not synchronized with the IRT clock. An internal
substitute clock is generated.
Flashing light Control Unit task system has synchronized with the IRT clock and data is being
exchanged.
Sync
Green
Continuous
light
Task system and MC-PLL have synchronized with the IRT clock.