Technical data

Diagnostics
3.1 Diagnostics via LEDs
Commissioning Manual
192 Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
3.1.3.4 Sensor Module Cabinet SMC10 / SMC20
Table 3- 42 Sensor Module Cabinet 10 / 20 (SMC10 / SMC20) – description of the LEDs
LED Color Status Description, cause Remedy
- off Electronics power supply is missing or outside permissible
tolerance range.
Green Continuous The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
Orange Continuous DRIVE-CLiQ communication is being established.
Red Continuous At least one fault is present in this component.
Note:
LED is driven irrespective of the corresponding messages
being reconfigured.
Remedy and
acknowledge fault
0.5 Hz
flashing
light
Firmware is being downloaded. Green/
red
2 Hz
flashing
light
Firmware download is complete. Wait for POWER ON Carry out a POWER
ON
RDY
READY
Green/
orange
or
Red/
orange
Flashing
light
Component recognition via LED is activated (p0144)
Note:
Both options depend on the LED status when component
recognition is activated via p0144 = 1.