Technical data
Diagnostics
3.1 Diagnostics via LEDs
Commissioning Manual
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
181
3.1.2.11 Control Interface Module in the Basic Line Module chassis format
Table 3- 26 Meaning of the LEDs "Ready" and "DC Link" on the Control Interface Module in the Basic Line Module
LED, state
Ready DC link
Description
Off Off The electronic power supply is missing or out of tolerance.
Off The component is ready for operation and cyclic DRIVE-CLiQ communication is taking
place.
Orange The component is ready for operation and cyclic DRIVE-CLiQ communication is taking
place.
The DC link voltage is present.
Green
Red The component is ready for operation and cyclic DRIVE-CLiQ communication is taking
place.
The DC link voltage is too high.
Orange Orange DRIVE-CLiQ communication is being established.
Red --- This component has at least one fault.
Note:
The LED is activated regardless of whether the corresponding messages have been
reconfigured.
Green / red
flashing light
0.5 Hz
--- Firmware is being downloaded.
Green / red
flashing light
2 Hz
--- Firmware download is complete. Wait for POWER ON.
Green /
orange
or
red / orange
flashing light
2 Hz
--- Component detection using LED is activated (p0124)
Note:
Both options depend on the LED state when activated via p0124 = 1.
Table 3- 27 Meaning of the LED "POWER OK" on the Control Interface Module in the Basic Line Module
LED Color State Description
Off DC link voltage < 100 V and voltage at -X9:1/2 less than 12 V.
On The component is ready for operation.
POWER OK Green
Flashing
light
There is a fault. If the LED continues to flash after you have performed a
POWER ON, please contact your Siemens service center.
WARNING
Hazardous DC link voltages may be present at any time regardless of the state of the "DC
link" LED.
The warning information on the component must be carefully observed!










