Technical data
Diagnostics
3.1 Diagnostics via LEDs
Commissioning Manual
178 Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
3.1.2.8 Motor Module booksize compact format
Table 3- 22 Meaning of the LEDs on the Motor Module booksize compact
State Description, cause Remedy
RDY DC LINK
Off Off Electronic power supply is missing or outside
permissible tolerance range.
–
-- The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
–
Orange The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is present.
–
Green
Red The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is too high.
Check the line voltage
Orange Orange DRIVE-CLiQ communication is being established. –
Red -- This component has at least one fault.
Note:
The LED is activated regardless of whether the
corresponding messages have been reconfigured.
Remedy and acknowledge
fault
Green/red
(0.5 Hz)
-- Firmware is being downloaded. –
Green/red
(2 Hz)
-- Firmware download is complete. Wait for POWER ON. Carry out a POWER ON
Green /
orange
or
red/orange
-- Detection of the components via LED is activated
(p0124).
Note:
Both options depend on the LED state when activated
via p0124 = 1.
–
DANGER
Hazardous DC link voltages may be present at any time regardless of the state of the "DC
LINK" LED.
The warning information on the component must be carefully observed!