Technical data
Diagnostics
3.1 Diagnostics via LEDs
Commissioning Manual
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
175
3.1.2.5 Single Motor Module / Double Motor Module / Power Module
Table 3- 19 Meaning of the LEDs on the Motor Module
State Description, cause Remedy
Ready DC link
Off Off Electronic power supply is missing or outside
permissible tolerance range.
–
Off The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
–
Orange The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is present.
–
Green
Red The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is too high.
Check the line voltage
Orange Orange DRIVE-CLiQ communication is being established. –
Red – This component has at least one fault.
Note:
The LED is activated regardless of whether the
corresponding messages have been reconfigured.
Remedy and acknowledge
fault
Green / red
flashing light
0.5 Hz
– Firmware is being downloaded. –
Green / red
flashing light
2 Hz
– Firmware download is complete. Wait for POWER ON. Carry out a POWER ON
Green /
orange
or
Red / orange
– Component detection via LED is activated (p0124).
Note:
Both options depend on the LED state when activated
via p0124 = 1.
–
DANGER
Hazardous DC link voltages may be present at any time regardless of the state of the "DC
link" LED.