Technical data
Commissioning
2.10 Commissioning of power units connected in parallel
Commissioning Manual
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
115
Parallel connection of infeeds in STARTER
Figure 2-26 Example of parallel connection of 3 Active Line Modules (chassis type)
You need to specify the number of infeeds to be connected in parallel in the appropriate field
(maximum 8 infeeds).
You can also choose possible Master/Slave function for the Active Line Modules using an
option on this screen (see SINAMICS S120 Function Manual, chapter "Master/slave function
for infeeds").
The line filter is offered as an option, depending on the infeed. An Active Interface Module
(AIM) with integrated line filter is required to operate an "Active Line Module" (ALM). We
recommend external line filters to operate the "Basic Line Module" (BLM) and "Smart Line
Module" (SLM) infeeds.