Technical data

Commissioning
2.8 First commissioning, control mode vector AC Drive in the booksize format
Commissioning Manual
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
109
Procedure Description Factory
setting
13. p1035[0] =
r0019.0013
(DO 1)
BI: Motor potentiometer setpoint higher [CDS]
Sets the signal source to increase the setpoint for the motorized potentiometer
Interconnection with r0019.013 of the drive object Control Unit (DO 1)
Effect: Signal, motorized potentiometer setpoint higher from BOP
0
14. p1036[0] =
r0019.0014
(DO 1)
BI: Motor potentiometer setpoint lower [CDS]
Sets the signal source to reduce the setpoint for the motorized potentiometer
Interconnection with r0019.014 of the drive object Control Unit (DO 1)
Effect: Signal, motorized potentiometer lower setpoint from BOP
0
15. p1070[0] =
r1050 (DO 63)
CI: Main setpoint [CDS]
Sets the signal source for speed setpoint 1 of the speed controller.
Interconnection with r1050.000 to the separate drive object (DO 63)
Effect: Motorized potentiometer supplies the speed setpoint
0
16. "FN", then press "P". The display indicates 41, press "O", the display jumps to 31.
17. Start the motor data identification with "I". The drive switches off again after approx. 5 sec. the display goes back to
41.
18. 31 is displayed again after pressing "O", the drive is now ready. The drive is switched on by pressing "I", the motor
accelerates by pressing the "arrow up" key.
19. Save all
parameters
Press the P key for approx. 5 sec until the display flashes.
* These parameters offer more setting options than the ones described here. For further setting options see
SINAMICS S120/S150 List Manual
[CDS] Parameter depends on command data sets (CDS). Data set 0 is preset.
[DDS] Parameter depends on drive data sets (DDS). Data set 0 is preset.
[MDS] Parameter depends on motor data sets (MDS). Data set 0 is preset.
BI binector input
BO binector output
CI connector input
CO connector output