Technical data
Commissioning
2.8 First commissioning, control mode vector AC Drive in the booksize format
Commissioning Manual
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
105
2.8 First commissioning, control mode vector AC Drive in the booksize
format
The example provided in this section explains all the configuration and parameter settings,
as well as the tests that are required for initial commissioning. Commissioning is carried out
using the STARTER commissioning tool.
Requirements for commissioning
1. The commissioning requirements have been met according to Section 1.1.
2. The check list - Table 1-1 or 1-2 from the Chapter Preparing for commissioning - has
been filled out and the points complied with.
2.8.1 Task
1. A drive unit is to be commissioned (operating mode vector, closed-loop speed control),
without DRIVE-CLiQ and without speed encoder with the following components:
Table 2- 14 Component overview
Designation Component Order number
Closed-loop control
Control Unit Control Unit 310-2DP 6SL3040-1LA00-0AA0
Operator Panel Basic Operator Panel BOP20 6SL3055-0AA00-4BAx
Infeed and drive
Power Module Power Module 340 6SL3210-1SB14-xxxx
Motor Induction motor
(without DRIVE-CLiQ interface)
1LA7
2. Commissioning is performed using the BOP20.
3. The function keys on the BOP20 must be parameterized so that the ON/OFF signal and
speed settings can be defined via these keys.