Technical data
Commissioning
2.7 First commissioning, vector control mode in the chassis format
Commissioning Manual
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
103
What to do? How to do it? Comment
Ramp-function
generator
Ramp-function generator
p1140 = 1 Ramp-function generator enable
p1141 = 1 Ramp-function generator start
p1142 = 1 Enable setpoint
See function diagram [3060]
4.3
Setpoint
Specify setpoint
p1001 = 0 Fixed setpoint 1
p1002 = 40 Fixed setpoint 2
p1020 = r0722 Fixed speed setpoint selection
r1024 = p1070 Fixed setpoint active
A setpoint of 0 (0 signal) or 40 (1
signal) is defaulted via digital input
7. This setpoint is then applied to
the main setpoint p1070.
See function diagram [3010]
4.4
5. Load parameters to
device
Connect with target system (go online)
Target device –> Load to target device
Position cursor on drive unit and
right-click.