Technical data
Commissioning
2.7 First commissioning, vector control mode in the chassis format
Commissioning Manual
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
101
What to do? How to do it? Comment
3.2 Power unit The wizard displays the data determined
automatically from the electronic rating plate.
Caution
If a sine-wave filter is connected,
then it must be activated here as
otherwise it could be destroyed!
Caution
If the infeed is controlled by a different Control Unit, the "Ready" signal for the infeed r0863.0 must be interconnected with
drive parameter p0864 "Infeed ready" via a digital input/output. If this is not taken into account, the infeed may be
damaged.
3.3 Drive setting You can select the motor standard (IEC/NEMA) and
power unit application (duty cycles).
3.4 Motor The name of the motor (e.g. equipment marking) can
be entered.
Enter motor data: Yes
Select motor type "1LA8"
You can select a standard motor
from the list of motors or you can
enter the motor data yourself. You
can then select the motor type.
3.5 Motor data You can enter the motor data on the rating plate
here.
If known, mechanical data for the motor and drive
train can be entered.
Equivalent circuit diagram data: No
If you do not enter any mechanical
data, it is estimated on the basis of
the data on the rating plate.
The equivalent circuit diagram data
is also estimated on the basis of
the data on the rating plate or
determined by means of automatic
motor data identification.
3.6 Motor brake Here, you can configure the brake and activate the
"Extended brake control" function module.
For more information, see the
Function Manual.
3.7 Encoder Choose standard encoder from list: Yes
Choose "1024 HTL A/B R to X521/X531".
If you are using an encoder that is
not in the list, you can also enter
the data.
3.8 Drive functions You can choose the application and motor data
identification here.
Motor data identification: "1"
Your choice of application
influences the calculation for the
open-loop/closed-loop control
parameters.
When the pulses are enabled, a
single motor data identification run
is carried out. Current flows
through the motor which means
that it can align itself by up to a
quarter of a revolution. Once the
measurement is complete,
optimization with rotating motor is
carried out the next time the pulses
are enabled.
3.9 Important parameters You must enter important parameters in accordance
with the relevant application.
Note, for example, the general mechanical
conditions for the drive train.