Instructions / Assembly

WARNING
OTHER
HAZARDS
Installation Instructions
BEFORE YOU INSTALL: Install only one type of exhaust vent, remove or plug any existing vents
(gable vents, roof louvers, wind turbines and power fans). Install adequate intake ventilation for a
balanced system (50% Exhaust & 50% Intake) in accordance with state and local code requirements.
Intake vents must be installed low at the roof’s edge or in the soft/undereave. Products such as Air
Vent’s Continuous Soft Vent, Vented Drip Edge, Undereave Vents and The Edge™ Vent provide the
necessary intake ventilation for optimum performance.
ROOF PITCH: Fit roofs with 3/12 to 18/12 pitches.
NFA: 15 sq. in. per linear foot
TOOLS REQUIRED:
• Utility knife
• Chalk line
• Roong nails
(if nails provided are not adequate)
• Tube of ASTM D4586
compliant roof sealant and
caulking gun
• Tape measure
• Circular saw
• Nail Gun or hammer
(regulate nail gun pressure as needed)
• Appropriate OSHA compliant
safety and personal protective
equipment
IMPORTANT NOTES BEFORE INSTALLING:
1. Run the ridge vent from end to end on the roof ridge for an attractive appearance.
2. Carefully secure the ridge vent prior to cap shingle nailing. (see Figure 1)
3. Installer should verify adequate nail length prior to installation. All nails must fully
penetrate the deck (see Figure 1 for proper nailing).
• If a longer nail is required to fully penetrate the deck, it must be 11
or 12 gauge and corrosion-resistant with at least a 3/8” head.
Installation Steps
Includes Nails
Note: It is the installer's responsibility
to ensure that the nail fully penetrates
the roof deck.
Fast & Easy Installation
Roll it out. Nail it down
D
O
N
T
M
I
X
V
E
N
T
T
Y
P
E
S
Roof Slot - Ridge
1. Ridge Vent:
A. SEE DIAGRAM 1 & 2.
Cut a 1.5" wide slot along the roof ridge line, (3/4"on either side of center), but leave 12" at each end uncut. Cut only through
the sheathing. Do not cut roof trusses. (On buildings with a ridge board, cut a 3" slot, 1.5" on each side of the ridge line.)
B. SEE DIAGRAM 3 & 4.
Lay out the location of the slots to be cut, ensure the length of the slots equals the minimum amount of RidgeHawk required.
Slots must end:
• 6 inch from rake edge or 6 inch from inside gable wall. [Diagram 3] • 12 inch from any ridge line obstruction, such as
a chimney. [Diagram 3]
• 12 inch from any intersection on a “T” or “L” roof. [Diagram 4]
Warning: The slot can be cut before or after shingle application however, for proper ventilation, care must be taken to
ensure that no roong material covers the ventilation slot.
Install Sht Part AV0952 REV A
© 2021 Air Vent Inc.
Includes 1 Nails
3/4”
Note: Nails must penetrate roof decking
Fast and Easy Installation
Roll it out, Nail it down
Figure 1
Page 1 of 3