INSTALLATION AND OPERATING MANUAL Series GS Richter Strainers Keep for future use! This operating manual must be strictly observed before transport, installation, operation and maintenance Subject to change without notice. Reproduction is generally permitted with indication of the source.
Series GS Page 2 List of Contents List of Contents 2 Relevant documents 2 1 Technical data 3 1.1 Name plate, CE and body markings ............ 3 1.2 Tightening torques ....................................... 4 1.3 Pressure/temperature diagram ................... 4 2 Notes on safety 5 2.1 Intended use ................................................ 5 2.2 For the customer / operator ......................... 5 2.3 Improper operation ......................................
Series GS 1 Page 3 Technical data Manufacturer: Dimensions and individual parts: Richter Chemie-Technik GmbH Otto-Schott-Str. 2 D-47906 Kempen Telephone : +49 (0) 2152 146-0 Fax: +49 (0) 2152 146-190 E-Mail : richter-info@idexcorp.com Internet: http://www.richter-ct.com See sectional drawing in Section 10 Designation : 1.
Series GS 1.2 Page 4 Cover screws Tightening torques All screws greased, tighten in diametrically opposite sequence! The tightening torques for pipe screws and body screws mentioned must not be exceeded. For an exception, see Section 8, Flange connection valve / pipe is leaking. The following tightening torques are recommended. Pipe screws, flanges to ISO/DIN Flange nom.
Series GS 2 Page 5 Notes on safety This operating manual contains fundamental information which is to be observed during installation, operation and maintenance. It must therefore be read before installation and commissioning! For valves which are used in potentially explosive areas, see Section 3. Installation and operation are to be performed by qualified staff. The area of responsibility, authority and supervision of the staff must be regulated by the customer.
Series GS 3 Page 6 Safety notes for applications in potentially explosive areas based on the Directive 94/9/ EC (ATEX 95) The valves are intended for use in a potentially explosive area and are therefore subject to the conformity assessment procedure of the directive 94/9/EC (ATEX).
Series GS 4 Page 7 Safety note for valves, certified to Clean Air Act (TA Luft) On request, this valve can be supplied compliant with the German Clean Air Code. Certificate / Manufacturer Declaration Validity is dependent on the operating instructions being read and observed. 5 In particular, servicing must be conducted at regular intervals, and the bolted connections relevant for tightness must be inspected and retightened if necessary.
Series GS 6 Page 8 Installation Examine valve for in-transit damage, damaged globe shut-off or control valves must not be installed. 6.2 Before installation the valve and the connecting pipe must be carefully cleaned to remove any dirt, especially hard foreign matter. The direction of flow must be observed when installing the valve. It is indicated by a direction arrow on the valve shell.
Series GS 8 Page 9 Malfunctions Clogged strainer basket Remove and dismantle entire strainer basket, clean or replace and install again. See Sections 9.1 and 9.2. Strainer basket sticks If functional parts swell owing to the medium, it is very difficult to remove the strainer basket. 9 Flange connection valve/pipe is leaking Retighten the flange screws to a tightening torque according to Section 1.2. If this does not remedy the leak, the recommended torques may be exceeded by 10%.
Series GS 10 Page 10 Drawing 10.1 Sectional drawing 100 106 109 205 216 220 includes: 218 222 234 body cover transition cover seat filter web * strainer basket compl. 9540-060-en TM 6506 strainer basket bottom strainer basket (interior) strainer basket (exterior) Revision 05 Edition 05/2006 522 901/1 902/1 920/1 936/1 * round cord hex. screw stud screw (DN 100) hex.
Series GS Page 11 10.2 Dimensional drawing Face to face acc. to ISO/DIN, PN 16 DN 15/20 25 40 50 65 80 100 L 130 160 200 230 290 310 350 H 112 156 197 205 205 313 327 A ca. 100 ca. 130 ca.160 ca. 160 ca. 160 ca. 230 ca. 240 dimensions in mm Face to face acc. to ANSI/ISA 78.08.01, class 150 DN ½" / ¾" 1" 1½" 2" 2½" 3" 4" L 130 * 185 222 254 -- 298 350 * H 112 156 197 205 -- 313 327 A ca. 100 ca. 130 ca.160 ca. 160 -- ca. 230 ca.
A Unit of IDEX Corporation Konformitätserklärung nach Richtlinie 97/23/EG für Richter Chemie-Technik GmbH Armaturen Declaration of conformity according the directive 97/23/EG for Richter Chemie-Technik GmbH valves Hiermit erklärt die Richter Chemie-Technik GmbH die Konformität der gelieferten Armaturen gemäß der Richtlinie 97/23/EG (Druckgeräterichtlinie). Herewith Richter Chemie-Technik GmbH declares the conformity of the delivered valves according to the directive 97/23/EG (Pressure Equipment Directive).
Safety Information / Declaration of No Objection Concerning the Contamination of Richter-Pumps, -Valves and Components 1 SCOPE AND PURPOSE Each entrepreneur (operator) carries the responsibility for the health and safety of his employees. This extends also to the personnel, who implements repairs with the operator or with the contractor. Enclosed declaration is for the information of the contractor concerning the possible contamination of the pumps, valves and component sent in for repair.
Declaration about the Contamination of Richter Pumps, -Valves and Components The repair and/or maintenance of pumps, valves and components can only be implemented if a completely filled out declaration is available. If this is not the case, delay of the work will occur. If this declaration is not attached to the devices, which have to be repaired, the transmission can be rejected. Every aggregate has to have it’s own declaration.
FAX Fax No. () Pages (incl. cover sheet) () To: () Contact person: () Your order No.: Our Kom. No.: Reference: () () () Extension: - () E-Mail Address: () Date: () Serial No.: () Dear Sirs, The compliance with laws for the industrial safety obligates all commercial enterprises to protect their employees and/or humans and environment against harmful effects while handling dangerous materials.