Use And Care Manual
15
A. Water Heater Location
❑ Close to area of heated water demand.
❑ Indoors and protected from moisture,
wet conditions, freezing temperatures
(below 32°F) and High temperatures
(above 140°F).
❑ Area free of flammable vapours.
❑ Provisions for Air Cirulation (Louvered
doors on ducting).
❑ Provisions made to protect area from
water damage.
❑ Sufficient room to service heater.
❑ Six inches (6") of clearance from ceiling
to top of Hybrid Water Heater to allow
for filter maintenance.
❑ Access to condensate disposal.
❑ Vibration Isolation Kit (Non-Concrete
floors).
❑ Hybrid seismic Kit (if required)
B. Water Supply
F. Ducting
❑ Water heater completely filled with
water.
❑ Air purged from water heater and piping.
❑ Water connections tight and free of
leaks.
❑ Flexible water connections.
❑ HVAC approved ducting.
❑ Calculated length of duct no greater than
maximum allowed.
❑ UL Certified terminations (For ducting
to the outside).
❑ Insulated duct.
❑ Ducting adequately supported.
❑ Ducting adequately isolated from structure.
C. Relief Valve
❑ Temperature and Pressure Relief Valve
properly installed and discharge line run
to open drain.
❑ Discharge line protected from freezing.
D. Wiring
❑ Power Supply voltage agrees with water
heater rating plate.
❑ Branch circuit wire and fusing or circuit
breaker of proper size. (Recommended
30 amp breaker)
❑ Electrical connections tight and unit
properly grounded.
❑ 10 gauge wire.
E. Condensate Lines
❑ Condensate lines from heat pump
installed correctly.
❑ Condensate lines from heat pump run to
a suitable drain location.