User manual
Set the INPUT LIMIT (P-03)
The current available to the Invertek depends on the source of the AC input supply,
i.e. motor generator, limited grid supply in a caravan park or shore power. The
value of the “INPUT LIMIT” P-03 adjustment must be lower or equal to the current
available from the AC Input source. For example if you have a generator of 2kW
you must adjust the “Input limit” to approximately 8.5A. To calculate this, divide the
nominal power of the AC input source (2000W) by the voltage (230V). If the circuit
breaker before the Invertek is lower than this value, then you must set the “Input
Limit” to the value of the circuit breaker.
Generator power Current (230V)
500W 2A
900W 4A
1500W 6,5A
2000W 8,5A
3000W 13A
G.1.4 Set the charging current (P-02):
The maximum charging current or the battery can be adjusted the Parameters P-02
. The charging current should be set to approximately 10-15% of the battery
capacity (at C10). This means that the charging current for a battery with 300Ah
should be set between 30-45A. The charging current is displayed on the
“multi-display” or “CURRENT MONITOR” on the front panel
G.1.5 Battery Condition:
The built in microprocessor features a specially developed algorithm (formulae)
which calculates the actual state of charge (SOC) of the battery and displays it on
LED-8. The Equalize LED-7 is lit when the system is performing an equalization
charge. The SOC displayed should be used as a guide only, for batteries which
are not sealed, use a hydrometer to determine the exact SOC.
For Safety reasons. You must get the recommended charge voltage and charge
current from your battery supplier. The voltage levels and charge characteristics
can be changed through “Parameters P-12,P-13,P-14,P-15 and P-16”. The correct
charging levels are critical for safe functioning and long life of the battery.
-23-
Batter
y
0~25%
Batter
y
25~50%
Battery 50~75%
Batter
y
75~100%
8. Battery
7.