User manual

P-13 Absorption
Voltage
1 0 4 0 : 14.2V/28.4V/56.8V
1 : 14.4V/28.8V/57.6V
2 : 14.6V/29.2V/58.4V
3 : 14.8V/29.6V/59.2V
4 : 15.0V/30.0V/60.0V
P-14 Absorption
Time
2 0 4 0 : 1Min
1 : 1HR
2 : 2HR
3 : 3HR
4 : 4HR
P-15 Float Voltage 2 0 4 0 : 13.3V/26.6V/53.2V
1 : 13.4V/26.8V/53.6V
2 : 13.5V/27.0V/54.0V
3 : 13.6V/27.2V/54.4V
4 : 13.7V/27.4V/54.8V
P-16 Equalize
Voltage
2 0 4 0 : 15.1V/30.2V/62.0V
1 : 15.2V/30.4V/61.6V
2 : 15.3V/30.6V/61.2V
3 : 15.4V/30.8V/60.8V
4 : 15.5V/31.0V/60.4V
P-17 Software
version
Read only
Note 1 : Aux.1/2 Contact function selection1(bit0) -
Aux.1 /2Contact function selection 1(bit1) - battery status 25%
Aux.1/2 Contact function selection 1(bit2) - battery statuts50%
Aux.1/2 Contact function selection 1(bit3) - battery status75%
Aux.1/2 Contact function selection 1(bit4) - battery stattus100%
Aux.1/2 Contact function selection 1(bit5) - In Equalize Cycle
Aux.1/2 Contact function selection 1(bit6) - SOLAR CHARGER action
Aux.1/2 Contact function selection 1(bit7) - CHARGER action
Note 2 : Aux.1/2 Contact function selection 2(bit0) – AC IN action
Aux.1/2 Contact function selection 2 (bit1) – BYPASS action
Aux.1/2 Contact function selection 2 (bit2) – AC OUT action
Aux.1/2 Contact function selection 2 (bit3) – INVERTER action
Aux.1/2 Contact function selection 2 (bit4) – Over Temperature
Aux.1/2 Contact function selection 2 (bit5) – Over Load
Aux.1/2 Contact function selection 2 (bit6) – Battery Low/High
Aux.1/2 Contact function selection 2 (bit7) – STOP
-15-