Specifications
Model SC-1500 (12V/24V) SC-3000 (12V/24V) CP-1500 (12V) CP-3000 (24V)
INVERTER
InputVoltageRange(VDC) 12V:9.5-16V,24V:19-32V
OutputVoltage(VAC) 210~240VAC
OutputFrequency 50Hz+/-1%
OutputWaveform LowFrequencyTruePureSinewave
THD <5%
PowerFactor AllLoads
Switch-on Behavior Nominaloutputvoltagewithin20msec
Cont.OutputPowerUnder70°C(W)(cosө=1.0) 1500W 3000W 1500W 3000W
MaximumPower(W) 3000W 6000W 3000W 6000W
SurgePower(W) 4500W 9000W 4500W 9000W
MaximumEfciency(%) 12V:82%,24V:84% 12V:84%,24V:86% 12V:82% 24V:86%
Zero-loadPower(W) 12W(8Wpowersave) 18W(12Wpowersave) 12W(8Wpowersave) 18W(12Wpowersave)
AC CHARGER
InputVoltageRange(VAC) 180~270VAC
InputFrequency 45-55Hz
PowerFactor 1
Charge Characteristic 4-Stageadaptive/Bulk-Absorption-Float-Equalize+Safe
MaximumDCVoltageRipple(Vrms) <1.25V
OutputChargingVoltage(VDC) 12V:12~16VDC,24V:24~32VDC
AbsorptionVoltageDefault(VDC) 12V:14.4VDC,24V:28.8VDC
FloatVoltageDefault(VDC) 12V:13.8VDC,24V:27.6VDC
EqualizeVoltageDefault(VDC) 12V:13.2VDC,24V:26.4VDC
OutputChargeVoltage(VDC)min/max 12V:8~16VDC,24V:11~32VDC
ChargeCurrentHouseBattery(A) 12V:70A,24V:40A 12V:140A,24V:70A 12V:70A 24V:70A
ChargeCurrentStarterBattery(A) 4A
AC INPUT SWITCH
InternalThermalCircuitBreaker 15A 30A
Switch-overTimeInvertertoACInput 0msec
Switch-overTimeACInputtoInverter 0msec
DetectionTimeACInputFault 4~10msec
TripLevelACLowInputtoInverter 180~230VAC(Default180VAC)
TripLevelInvertertoACLowInput 181~231VAC(Default187VAC)
TripLevelInvertertoACHighInput 229~269VAC(Default265VAC)
TripLevelACHighInputtoInverter 230~270VAC(Default270VAC)
Min-MaxFrequencyRange(50Hz) 45-55Hz
SOLAR CHARGER MODULE [SS-45C & SS-60C (OPTIONAL)]
System voltage 12V,24V,36V,48V(panelvoltagemustmatchbatteryvoltage)
MaxSolarVoltage(Voc) 140V
MaxOperatingvoltage 68V
ControllerPowerConsumption <25mA(IncludingLCD)
SolarPVCurrent 45A/60A
ParallelConnection(Stackable) YESx10units YESx10units
Charging Characteristic TruePulseWidthModulation(PWM)
DC GENERATOR MODULE (OPTIONAL)
SystemVoltage 12V/24V
N/A
Current 140A/70A
ParallelConnection(Stackable) YESx5units
DC CONTROLLER 1 & 2 MODULE (OPTIONAL)
SystemVoltage 12V/24V
N/A
Current 140A/70A
ParallelConnection(Stackable)2x5units YESUpto700Amps
TimerFunction DCController2
LowVoltageDisconnect/Reconnect DCController1&2
AC GENERATOR AUTOMATIC TRANSFER SWITCH (OPTIONAL)
InputVoltageRange 190-240VAC
FrequencyRange50Hz 45~55Hz
Switching Capacity 20A
TripLevelMastertoSlave <180VAC
TripLevelSlavetoMaster >188VAC
SwitchingTime <12msec
PowerContinuousStabilityInterval 30sec
OPTIONAL ACCESSORIES
Solar Charge Controller SunStar solar controllers for control of solar charging
DCGeneratorInput DCgeneratormoduleforextrasourceofDCcharging
DCLoadControl(SW1) Lowvoltagedisconnect/reconnectforDCloads
DCLoadControl(SW2) Lowvoltagedisconnect/reconnectandcutin/outtimerforDCloads
Remote Control Fulldisplayuserpanelforremotecontroloperationandmonitoring.
BatteryTempSensor Batteryovertemperatureprotection&toprovidecorrectchargingcharacteristics
PCRemoteInterface PCConnectionkitallowingremotemonitoring,programmingandlogging
StackingHUB
AllowsCombiPlus&SuperCombitobestackedtogether.
AllowsCombiPlus&SuperCombitobeconnectin2&3Phaseconguration.
DataLeads DataLeadsavailableindifferentlengthsforconnectiontoAccessories.
Remote Control Panel
Inmostinstallations,theCombiinverterandbatterybankwillbe
installedinashed,garage,orotherlocationoutsidethemainhome/
building, where it is inconvenient to view the current status of the
power system. By using the remote control panel, a complete replica
ofthefrontpaneloftheSuperCombiorCombiPluscanbeinstalledin
a more convenient location inside the property, giving full control and
monitoring without having to venture out to wherever the Combi unit
is installed.
Battery Temperature Sensor
An absolute must for any installation, and cheap insurance against
damagetotheveryexpensivebatterybank.Installingthebatterytemp
sensor tells the Combi what temperature the battery is operating at, so
that the Combi can adjust charging voltage and current accordingly, to
avoid permanent damage to the batteries. Batteries do get hot under
heave loads, so it is important to adjust charging accordingly.
Parallel and Multi-Phase Stacking Hubs
WhenwantingtostackmultipleCombiSeriesunitstogetherforextra
powerormulti-phaseoutput,youwillneedthesestackinghubs.Oneis
for parallel stacking for boosting power, and the other is for providing
multiple-phase AC output.
CombiNet Data Leads
ThedatacablerequiredtolinkaCombiSeriesinverterwithother
accessoryproductsontheCombiNetlink.A10-corecablewithRJ50
connectors,nottobeconfusedwithanormalCat5datalead.
Available in various lengths.
Systems and Accessories
Combi Series Inverter-Charger System Specifications
Model SC-1500 (12V/24V) SC-3000 (12V/24V) CP-1500 (12V) CP-3000 (24V)
GENERAL
PowerSharing(InverterPowerBoosting) 10A 20A 10A 20A
AutoTransferSwitch(ATS)Generator/ACInput 16A 32A 16A 32A
MaximumCombinedPowerOutput(Inverter+ATS) 25A 50A 25A 50A
TwoandThreePhasePowerOptions YES
ParallelOperation(Stackable) YES(Max5xunitssinglephase/15xunits3-phase)
GreenPowerSmartFunction YES
AdvancedGreenPowerSmartFunction
(withACChargerTimerFunctionwithGeneratorTimer)
YES NO
MultiPurposeRelay 3RelaysFullyProgrammable(AutoStartforGenerator)
Protection
Outputshortcircuit,Overload,BatteryOvervoltage/Undervoltage,Batteryreversepolaritydetection,
Highinputvoltageripple,DCvoltageripple.OverTemperatureProtection:Transformer105°C,
Electronic&Powerstage70°C,Batterytemperature50°C
OperatingTemperatureRange Operatingtemprange-20°Cto70°C(Fanassistedcooling)Humidity:Max95%(noncondensing)
Cabinet/ProtectionClass Aluminum/IP20
Weight(kgs) 21kg 27kg 21kg 27kg
Dimensions(HxWxD)mm 362x258x370mm 424x258x370mm 362x258x370mm 424x258x370mm