Specifications
6
Dip Switch 7
ON: Lighting control
OFF: Load Control
OFF:
Lights remain turned off.
2,4,6,8,10: Hours light is turned on after sunset.
2/1, 3/1, 4/1,
6/1, 2/2, 3/2,
4/2, 6/2,
8/2:
Light is turned on after sunset, turned off after the selected
lasting hours, and turned on again before sunrise.
2/1: Light is turned on for two hours after sunset, turned off
after two hours and turned on again one hour before sunrise.
Lighting control
Switch
D/D: Dusk-to-Dawn, light is on all night
Remote Panel Connecting port for the optional LCD remote panel for SW-30CL model
BVS + /–
Connecting terminal for Battery Voltage Sensor to compensate for voltage
loss due to cable resistance.
BTS
Battery Temperature Sensor is built in SunWide for temperature
compensation
LED Status Indicators
Charge Status LED
Blinking Green: Charging is in the state of Bulk or Absorption
Solid Green: Charging is in the state of Float
Solid Orange: Charging in the state of Equalization
Solid Red: Charging in the state of fault: Over Current
Blinking Red: Charging in the state of fault: Over Temp.
※ SunWide units do the auto detection for day and night with the solar array
for the first day of installation so every SunWide unit must go through the
following two procedures when used in “Light Control Mode”.
Blinking Green/Red by turns:
The solar array has been detected to be less than 6V for lasting 10 minutes
and SunWide recognizes the time as nighttime.
Blinking Orange/Green by returns:
The solar array has been detected to be more than 10V for lasting 10 minutes
and SunWide recognizes the time as daytime.
Load Status LED
Blinking Green:
If the battery charge state falls below the disconnect setpoint voltage (Initial
setting: 11.1V for 12V system, 22.2V for 24V system and 44.4V for 48V
system) lasting for six minutes, the green LED will blink to be ready for load
disconnection.
Solid Orange:
After six minutes of battery voltage under setpoint, the orange LED will lit to
show the low voltage disconnection for loads.
Blinking Orange:
When the battery voltage recovers to above the reconnect setpoint (Initial
setting: 12.6V for 12V system, 25.2V for 24V system and 50.4V for 48V
system), the orange LED will blink to be ready for reconnection for six
minutes.