Instructions / Assembly

33
To be able to use a PVC termination, a short piece of PP pipe will need to be cut, as shown below, to transition from the bell end of
the pipe to the PP to PVC adapter.
A. Water Heater Location
Close to vent locations
Located indoors and protected from freezing temperatures
Proper clearance from combustible surfaces
Air supply free of corrosive elements and flammable vapors
Sufficient room to service the heater
Water heater protected from water damage
B. Water Supply
Water heater completely filled
Air purged from water heater and piping
Water connections tight and free of leak
C. Gas Supply
Gas line equipped with shut-off valve, union, and sediment
trap
Minimum pipe size 1/2"; No flex pipe
Soap and water solution used to check all
connections for gas leaks
Approved pipe joint compound used
D. Relief Valve
Discharge line run to open drain
Discharge line protected from freezing
E. Venting
Water heater vented separately from all other appliances
All vent and air intake pipe connections are secure
Vent and air intake pipes properly supported at regular
intervals
Precaution on taken to avoid moisture damage around vent
termination
Drain tube attached to sound damper if needed. If not,
ensure cap is in place
F. Condensate
Condensate trap installed and primed.
Condensate neutralizer installed
G. Wiring
Correct power supply (120VAC)
Electrical connections are tight
Water heater is properly grounded with proper polarity.
INSTALLATION CHECK LIST
For maximum pipe capacity for installations in Canada, refer to CAN/CSA B149.1. For natural gas, refer to Tables A.1 through A.17. For propane (LP) gas, refer to Tables
B.1 through B.12.
Nominal Iron Pipe Size
Inches
Internal Diameter
Inches
Length of Pipe, Feet
10 20 30 40 50 60 70 80 90 100 125 150 175 200
1/2 0.622 132 90 73 62 55 50 46 43 40 38 34 31 28 26
3/4 .824 278 190 152 130 115 105 96 90 84 79 72 64 59 55
1 1.049 520 350 285 245 215 195 180 170 160 150 130 120 110 100
1 1/4 1.380 1,050 730 590 500 440 400 370 350 320 305 275 250 225 210
1 1/2 1.610 1,600 1,100 890 760 670 610 560 530 490 460 410 380 350 320
2 2.067 3,050 2,100 1,650 1,450 1,270 1,150 1,050 990 930 870 780 710 650 610
2 1/2 2.469 4,800 3,300 2,700 2,300 2,000 1,850 1,700 1,600 1,500 1,400 1,250 1,130 1,050 980
3 3.068 8,500 5,900 4,700 4,100 3,600 3,250 3,000 2,800 2,600 2,500 2,200 2,000 1,850 1,700
4 4.026 17,500 12,000 9,700 8,300 7,400 6,800 6,200 5,800 5,400 5,100 4,500 4,100 3,800 3,500
Length Pipe Table
For U.S. Installations
Maximum Capacity of Pipe in Cubic Feet of Gas per Hour for Gas Pressures of 0.5 psig or Less and a Pressure Drop of 0.3 Inch Water Column
Based on a 0.60 Specific Gravity Natural Gas; If 1.5 Specific Gravity L.P. Gas is used, multiply capacity by 0.63