Instructions / Assembly
23
2, 3 or 4 inch pipe
and fittings
Support
Bracket
Every 3' Max.
45° Terminal
Raise horizontal pipe
upward 1/8 in. per foot
(10 mm per m) min.
• Connect 1/2 in. I.D., flexible, PVC (or equivalent material), clear tubing to the
drain port.
NOTICE: The tubing must be of sufficient length to reach a floor drain, outside
the building or other required condensate disposal termination requirements
(Refer to local codes).
• Loop the drain tube so that it has a circular trap and secure the top and bot-
tom of the loop with wire ties or plastic zip ties as shown. DO NOT restrict any
portion of the drain tube. The loop and all sections of the tube must not be
restricted or collapsed.
• Fill the drain tube with water so that no combustion gases might vent into the
room.
• Route the drain tube to a floor drain or outside the building or refer to local
codes for any condensation requirements.
Wall
Water
Heater
Drain Pan
1 In. Max.
Typical Horizontal Direct Vent System
INSTALLATION
23
Drain
Tube
Silencer
Blower Air Inlet
Connection