Instructions / Assembly
21
• DO NOT terminate near soffit vents or crawl space or other area where condensate or vapor could create a nuisance
hazard or cause property damage.
• DO NOT locate the exhaust vent terminal where condensate or vapor could cause damage or could be detrimental to the
operation of regulators, relief valves, or other equipment.
• DO NOT locate the exhaust vent terminal over public area or walkways where condensate or vapor can cause nui sance or
hazard.
• DO NOT locate the vent terminal in proximity to plants/shrubs.
INSTALLATION
VENT INSTALLATION – Before proceeding, make certain
you understand the procedure and cautions covered in the
section “Joining Pipes and Fittings.”
POWER VENT INSTALLATION – Power venting is where
the indoor air is used and the exhaust is vented to the
outside. Venting may be run horizontally through an
outside wall or vertically through a roof through using
either 2" (5.1 cm), 3" (7.6 cm), 4" (10.2 cm) diameter
PVC, ABS or CPVC. This water heater is supplied with a
screened intake elbow and exhaust coupling referred to
as the air intake terminal and the exhaust vent terminal.
NOTE: Flexible PP vent kit is available for Power Vent
configurations, in 2" and 3" diameters. These kits should
be used for vertical venting only.
NOTICE:
Use of PVC cellular core (ASTM-F891), ABS Schedule
40, DWV cellular core (ASTM –F628), or Radel®
(polyphenylsulfone) in non-metallic venting systems is
prohibited.
In a horizontal application, it is important that condensate
not be allowed to buildup in the exhaust vent pipe. To
prevent this from happening, the pipe should be installed
with a slight upward slope of ¼” per foot. The vent
system must be supported every 5 feet of vertical run and
every 3 feet of horizontal run of vent pipe length.
Failure to properly support the vent piping with hangers
and clamps may result in damage to the water heater or
venting system.










