Instructions / Assembly

21
DO NOT terminate near soffit vents or crawl space or other area where condensate or vapor could create a nuisance
hazard or cause property damage.
DO NOT locate the exhaust vent terminal where condensate or vapor could cause damage or could be detrimental to the
operation of regulators, relief valves, or other equipment.
DO NOT locate the exhaust vent terminal over public area or walkways where condensate or vapor can cause nui sance or
hazard.
• DO NOT locate the vent terminal in proximity to plants/shrubs.
INSTALLATION
VENT INSTALLATION – Before proceeding, make certain
you understand the procedure and cautions covered in the
section “Joining Pipes and Fittings.”
POWER VENT INSTALLATION – Power venting is where
the indoor air is used and the exhaust is vented to the
outside. Venting may be run horizontally through an
outside wall or vertically through a roof through using
either 2" (5.1 cm), 3" (7.6 cm), 4" (10.2 cm) diameter
PVC, ABS or CPVC. This water heater is supplied with a
screened intake elbow and exhaust coupling referred to
as the air intake terminal and the exhaust vent terminal.
NOTE: Flexible PP vent kit is available for Power Vent
configurations, in 2" and 3" diameters. These kits should
be used for vertical venting only.
NOTICE:
Use of PVC cellular core (ASTM-F891), ABS Schedule
40, DWV cellular core (ASTM –F628), or Radel®
(polyphenylsulfone) in non-metallic venting systems is
prohibited.
In a horizontal application, it is important that condensate
not be allowed to buildup in the exhaust vent pipe. To
prevent this from happening, the pipe should be installed
with a slight upward slope of ¼” per foot. The vent
system must be supported every 5 feet of vertical run and
every 3 feet of horizontal run of vent pipe length.
Failure to properly support the vent piping with hangers
and clamps may result in damage to the water heater or
venting system.